BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
72/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5.3.49 OU_rr_uu_ErrorCode_Status (Multistate Input Object Type)
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Multistate Input, 31rruu)
R
R
Object_Name
CharacterString
“OU_rr_uu_ErrorCode_Status”
R
R
Object_Type
BACnetObjectType
MULTISTATE_INPUT (13)
R
R
Present_Value
Unsigned
1 ~ 255
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
255
R
R
State_Text
BACnetArray[N] of
CharacterString
-
O
-
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Alarm_Values
List of Unsigned
-
O
R*
Fault_Values
List of Unsigned
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured
You can check the error codes for each AC system on section
(section 12.1)