5.3.54 OU_rr_uu_LowNoiseOp_Status (Multistate Input Object Type)
Low noise operation status for an outdoor unit can be monitored.
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Multistate Input, 32rruu)
R
R
Object_Name
CharacterString
“OU_rr_uu_LowNoiseOp_Status”
R
R
Object_Type
BACnetObjectType
MULTISTATE_INPUT (13)
R
R
Present_Value
Unsigned
1 ~ 16
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
16
R
R
State_Text
BACnetArray[N] of
CharacterString
Check
Low Noise Opeation status below
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Alarm_Values
List of Unsigned
-
O
R*
Fault_Values
List of Unsigned
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured
Low Noise Operating status table
Low Noise Operation Status can be checked using the values in the following correspondence table.
Pesent_Value
Contents displayed in State_Text
Pesent_Value Contents displayed in State_Text
1
Not Set
9
2/-/-
2
-/-/E
10
2/-/E
3
-/A/-
11
2/A/-
4
-/A/E
12
2/A/E
5
1/-/-
13
3/-/-
6
1/-/E
14
3/-/E
7
1/A/-
15
3/A/-
8
1/A/E
16
3/A/E