BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
95/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5. Object Instance:
BACnet object instance. This can be a fixed number or a formula for the identification
of each element.
6. Units:
Units applied to each object.
7. NC:
Notification Class.
8. State text configuration:
Enums the State text to be shown.
9. Relinquish default value:
Indicates the current relinquish default value for this object.
10. COV:
Sets the COV increment value for this object.
11. #:
Internal gateway address for each register.
12. Device:
FGL device number associated to this register.
a) Edit Columns:
Enables or disables visible columns.
b) Import:
Imports a previous existing configuration. Only Excel format is supported.
c) Export:
Exports the current configuration. Only Excel format is supported.
d) Check table:
Checks the current configuration to make sure
Receive/Send
Send or receive the current configuration of the gateway.
Figure 8.11
Send and receive options