23
NOTE:
All (-)H1T air-handlers have 5 speed constant torque motors.
Speed tap 1 is for continuous fan. Speed tap 2 (low static) and speed tap 3 (high static) are for lower tonnage (1.5 or 2.5 tons). Speed tap 4 (low static) and
speed tap 5 (high static) are for higher tonnage (2.0 or 3.0 tons).
(-)H1T air handlers are always shipped from factory at speed tap 5.
The low static speed tap 2 (lower tonnage) and 4 (higher tonnage) are for external static pressures below 0.5” WC. The high static speed tap 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5” WC. Move the blue wire to the appropriate speed tap on the motor terminal block as required
by the application needs.
• The airflow for continuous fan (speed tap 1) is always set at 50% of the speed tap 4.
• The above airflow table lists the airflow information for air handlers with maximum heater allowed for each model.
3.13.3 AIR-FLOW PERFORMANCE DATA (continued)
3.13.3.2 (-)F1T (CONSTANT TORQUE ECM MOTOR)
Model/
Nominal
Cooling
Capacity
Manufacturer
Recommended
Air-Flow Range
(Max/Min) CFM
Blower Size/
Motor HP #
of Speeds
Motor
Speed
From
Factory
Motor
Speed
X-13
CFM Dry Delivery/filter/heaters/RPM/Watts
External Static Pressure-Inches W.C.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
852
823
792
770
738
713
690
847
881
915
949
989
1026
1057
162
151
144
168
182
196
178
669
628
593
552
510
—
—
669
713
760
806
852
—
—
80
87
82
94
86
—
—
973
945
922
896
872
852
833
956
991
1020 1054 1082 1117
1145
222
221
247
256
253
261
260
841
807
780
753
733
—
—
849
890
925
957
992
—
—
160
168
179
187
187
—
—
1145 1122
1084
1064
1055
1025
1002
767
780
797
820
855
900
954
240
237
239
245
274
276
306
1037 1005
956
924
894
—
—
798
845
901
945
980
—
—
199
213
196
226
237
—
—
1306 1268
1223
1195
1162
1128
1093
887
933
986
1019 1056 1096
1133
307
313
313
339
373
356
370
1201 1163
1129
1094
1065
1040
—
866
914
964
999
1032
—
—
278
286
301
324
348
—
—
(-)F1T24
1.5 tons
825/510
10×6 1/3 Hp
2 speed
dual voltage
5
5
3
2
(-)F1T24
2 tons
973/733
10×6 1/3 Hp
2 speed
dual voltage
5
5
(-)F1T36
2.5 tons
1145/894
10×8 1/2 Hp
2 speed
dual voltage
5
5
5
4
3
2
(-)F1T36
3 tons
1306/1040
10×8 1/2 Hp
2 speed
dual voltage
5
5
5
4