CHAPTER 3
Small Configuration
Installing Cables
3-121
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
3.19.9
Installing RICC Cable (Optical Shelf)
This procedure provides instructions for connecting to the RICC ports on the Optical shelf
backplane.
lists pertinent information for these cables.
shows the cable connector pinouts.
Note:
The RICC cable is only required for HUB configurations.
Step
Task
1
Connect the RJ-45 connector on one end of the RICC cable (21-332-xxx) to Main Optical
shelf backplane connector CN24, CN25, CN31, or CN32.
2
Connect the other end of the RICC cable to the appropriate Auxiliary Optical shelf backplane
connector indicated in
Table 3-16: RICC Cable Information (Small Configuration)
Cable Part
Number
Backplane Connector
Number
Cable
Description
Connector
Type
Cable Wire
Size
21-332-xxx
a
a
xxx = length in feet
CN24, CN25, CN31, and
CN32 (Main and Auxiliary
Optical shelves)
RICC
connection
RJ-45
24 AWG
Figure 3-91: Connector Pinouts, RICC Cable
1
2
3
4
5
6
7
8
TXP
TXN
RXP
RXN
m1
71
4a
u_
1
Revision 1, June 2009