Table
2-19
Power
cords
and
connector
shape
(PDU
of
an
expansion
rack)
Destination
Power
cord
type
Connector
shape
Common
For
200
V
power
supply
(*1)
-
For
single-phase
power
supply
connection
IEC60309
60A
2P+E
-
For
three-phase
delta
connection
IEC60309
60A
3P+E
-
For
three-phase
star
connection
IEC60309
30A
3P+N+E
IEC60309
32A
3P+N+E
IEC60320-C20
*1
The
following
two
types
of
power
cords
are
necessary
for
each
chassis
mounted
in
an
expansion
rack:
0.5
m
(1.6
ft.)
and
1.5
m
(4.9
ft.)
power
cords.
The
customer
needs
to
order
these
power
cords
for
each
chassis.
Note
-
For
chassis
with
plugs
that
have
a
lock
function,
confirm
that
the
chassis
have
a
15
A
(20
A
for
the
SPARC
M10-4/M10-4S)
overcurrent
protection
device.
If
they
do
not
have
that
device,
provide
15
A
(20
A
for
SPARC
M10-4/M10-4S)
overcurrent
protection
using
a
circuit
breaker
or
fuse.
The
plugs
with
a
lock
function
are
the
NEMA
L6-20,
L6-15,
and
other
plugs
that
are
not
parallel
two-pole
connectors
with
grounding
electrodes.
Table
2-20
Distribution
panel
breaker
capacity
on
the
equipment
side
Device
name
Power
supply
input
Distribution
panel
breaker
capacity
on
equipment
side
For
Japan/North
America/other
countries
For
Europe
SPARC
M10-4S
Single-phase
200
to
240
VAC
20
A
16
A
SPARC
M10-4
Single-phase
200
to
240
VAC
20
A
16
A
SPARC
M10-1
Single-phase
100
to
120
VAC
12
A
-
Single-phase
200
to
240
VAC
10
A
10
A
Expansion
rack
Single-phase
200
to
240
VAC
40
A
40
A
Expansion
rack
Three-phase
(delta)
200
to
240
VAC
35
A
35
A
Expansion
rack
Three-phase
(star)
380
to
415
VAC
24
A
24
A
2.9.3
Breaker
characteristics
The
breaker
characteristics
for
the
SPARC
M10
systems
must
be
taken
into
consideration
to
allow
the
devices
to
be
used
under
the
right
conditions.
Use
circuit
breakers
that
meet
the
following
special
conditions
for
the
distribution
panel
breakers
on
the
equipment
side.
lists
the
distribution
panel
breaker
capacity
on
the
equipment
side.
Fujitsu
M10/SPARC
M10
Systems
Installation
Guide
・
July
2015
60
Summary of Contents for M10 Series
Page 1: ...Fujitsu M10 SPARC M10 Systems Installation Guide Manual Code C120 E678 12EN July 2015 ...
Page 10: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 x ...
Page 156: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 142 ...
Page 176: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 162 ...
Page 208: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 194 ...
Page 240: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 226 ...
Page 252: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 238 ...
Page 290: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 276 ...
Page 310: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 296 ...
Page 336: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 322 ...
Page 368: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 354 ...
Page 374: ...Fujitsu M10 SPARC M10 Systems Installation Guide July 2015 360 ...