U41290-J-Z816-3-76
9
2.2 Installation Precautions and Specifications
Humidity
In operation
20 to 80% RH (no condensation)
Not in operation
8 to 80% RH (no condensation)
Heat dissipation
1 SB (8 CPUs)
8820 kJ/hr
(8360 BTU/hr)
6480 kJ/hr
(6142 BTU/hr)
2 SBs (16 CPUs)
14220 kJ/hr
(13478 BTU/hr)
11340 kJ/hr
(10748 BTU/hr)
Vibration
In operation
0.2 G
Not in operation
0.4 G
Noise (Note4)
60 dB (A)
50 dB (A)
Installation type
Rack-mount type (16 mount spaces) (Note5)
Note2: In model names, x is any letter from A to Z. Y is any letter from A to
Z or any digit from 0 to 9.
Note4: This noise level is an average of the values measured with the main
unit mounted in a 1800 mm (70.9 in) rack in an anechoic room. The
noise level measured with an installed main unit may exceed this
noise level because of ambient noise and sound reflection.
Note5: Without maintenance tray (not used by Fujitsu Siemens Computers).
Table 2.2 Installation specifications of the PRIMEPOWER900 main unit (3/5)
Item
Specifications
(Model name:
PW0XDRyyyx)
(Note2)
(Model name:
PW0X0CR1x,
PW0X0CR6x)