BX900S2
Operating Manual
61
Hardware installation
I
The service LAN port (pos. 1 in
figure 11 on page 60
) and the LAN ports
for blade server management (pos. 4 and 5 in
figure 11 on page 60
) must
be in different LAN subnetworks.
It is recommended to operate the management blade user interface in a
separate broadcast domain for the server management.
Ê
Connect the data cables according to the system configuration you require.
Ports on the front of the system unit
On the front of the system unit are the ports of the server blades for local
administration. For information on these, see the operating manuals for the
relevant server blades.
5.3.1
Cable routing
The cables are routed along the support uprights of the rack.
5.4
Connecting the system unit to the mains
The system unit has six bays for hot-swap power supply units. In the base
configuration, it is fitted with three power supply units.
V
CAUTION!
●
Read the information on determining how many power supply units
are required (see the "PRIMERGY BX900 S2 System Unit Upgrade
and Maintenance Manual").
●
The power supply units automatically adjust to a mains voltage
between 100 - 240 V. The system unit may only be used if the local
mains voltage is within the voltage range of the system.
●
The 2880 W power supply units may only be connected to 16 A
power outlets, a UPS, a 32 A power distribution unit, or CEE sockets.
When ordering the system unit, you must specify which socket type
is available at the installation location, so that the cables with the
appropriate C19 connectors can be supplied.
●
For the Japanese market:
The standard power supply units (Japanese version) may only be
connected to NEMA L6-20, IEC 60320-C20, or NEMA 5-15 sockets.