CX400 M4
Operating Manual
43
5
Starting up
V
CAUTION!
●
Follow the safety instructions in chapter
.
●
Do not expose the server enclosure to extreme environmental
conditions (see
"Ambient conditions" on page 79
). Protect the server
enclosure from dust, humidity and heat.
●
Make sure that the server enclosure is acclimatized for the time
indicated in this table before putting it into operation.
In the
, the temperature difference refers
to the difference between the operating environment temperature and
the temperature to which the server enclosure was exposed
previously (outside, transport or storage temperature).
Temperature difference (°C)
Minimum acclimatization time
(hours)
5
3
10
5
15
7
20
8
25
9
30
10
Table 3: Acclimatization time