background image

60

Operating Manual

 CX400 M4

Starting up

5.4

Connecting cables

5.4.1

Notes on connecting/disconnecting cables

V

CAUTION!

Always read the documentation supplied with the device you wish to 
connect.
Never connect, or disconnect cables during a thunderstorm.
Never pull on a cable when disconnecting it. Always take hold of the 
cable by the plug.
Follow the sequence described below to connect or disconnect external 
devices to or from the server:
Ensure that you wait for 10 seconds or more after shutdown before 
turning the server on.

Connecting cables

Ê

Switch off the server and equipment switches.

Ê

Disconnect all power cords from the properly grounded power outlets.

Ê

Connect all cables to the server and peripherals.

Ê

Connect all data communication cables into the utility sockets.

Ê

Connect all power cords into the properly grounded power outlets.

Disconnecting cables

Ê

Switch off the server and equipment switches.

Ê

Disconnect all power cords from the properly grounded power outlets.

Ê

Disconnect all data communication cables from the utility sockets.

Ê

Disconnect the relevant cables from the server and all the peripherals.

I

For connecting or disconnecting LAN cables, the server does not need 
to be powered off. To avoid loss of data teaming function has to be 
enabled.

Summary of Contents for PRIMERGY CX400 M4

Page 1: ...Operating Manual English FUJITSU Server PRIMERGY CX400 M4 Server Enclosure Operating Manual March 2019 ...

Page 2: ...tas de Copyright and Trademarks Copyright 2019 FUJITSU LIMITED All rights reserved Delivery subject to availability right of technical modifications reserved All hardware and software names used are trademarks of their respective manufacturers The contents of this manual may be revised without prior notice Fujitsu assumes no liability for damages to third party copyrights or other rights arising f...

Page 3: ...oard assemblies of the product and in the mouse and keyboard are limited life components Use of these components beyond their operating life may result in electrolyte leakage or depletion potentially causing emission of foul odor or smoke As a guideline in a normal office environment 25 C operating life is not expected to be reached within the maintenance support period 5 years However operating l...

Page 4: ...or high safety use Measures against momentary voltage drop This product may be affected by a momentary voltage drop in the power supply caused by lightning To prevent a momentary voltage drop the use of an uninterruptible power supply is recommended This notice follows the guidelines of Voltage Dip Immunity of Personal Computer issued by JEITA the Japan Electronics and Information Technology Indus...

Page 5: ...ith SATA BC SATA storage interfaces Please note that the usage and operation conditions differ depending on the type of HDD used For more information on the usage and operation conditions of each available type of HDD see the following internet address http jp fujitsu com platform server primergy harddisk ...

Page 6: ...Operating Manual CX400 M4 ...

Page 7: ...3 2 Features 19 3 3 Controls and indicators 21 3 3 1 Controls and indicators on the server enclosure front 21 3 3 1 1 Controls on the front panel 21 3 3 1 2 Indicators on the front panel 22 3 3 1 3 Indicators on the hot plug HDD SSD module 27 3 3 2 Controls and indicators on the server enclosure rear 28 3 3 2 1 Indicator on hot plug PSU 28 3 3 3 Indicators of the server nodes 28 4 Important inform...

Page 8: ...witching on the multi node server system for the first time 61 6 Operation 63 6 1 Switching the multi node server system on and off 63 6 2 Removing 2 5 inch HDD SSD modules 66 6 2 1 Removing a 2 5 inch HDD SSD module 66 6 2 2 Installing a 2 5 inch HDD SSD dummy module 67 6 3 Removing the hot plug PSU 68 6 4 Installing a server node 69 6 4 1 Removing the server node dummy module 69 6 4 2 Installing...

Page 9: ...nd data transmission and you will require a basic knowledge of the underlying operating system 1 1 Notational conventions The following notational conventions are used in this manual Text in bold Indicates references to names of interface elements Text in monospace Indicates commands Quotation marks Indicate names of chapters and terms that are being emphasized Ê Describes activities that must be ...

Page 10: ...10 Operating Manual CX400 M4 Introduction ...

Page 11: ...http www fujitsu com jp products computing servers primergy manual The complete PRIMERGY documentation set can also be downloaded as a DVD ISO image at ftp ftp ts fujitsu com images serverview manuals For Japan http www fujitsu com jp products computing servers primergy downloa ds 2 1 1 Documents for the server enclosure Document Description Safety Notes and Regulations manual 安全上のご注意 for Japan Im...

Page 12: ...wnload Windows OS at http manuals ts fujitsu com illustrated_spa res or from the CSS component view of the ServerView Operations Manager Glossary Available online Warranty manual 保証書 for Japan Important information on warranty regulations recycling and service available online or as a printed copy Additional documentation RAID documentation available online at http manuals ts fujitsu com under x86...

Page 13: ...MERGY CX2550 M4 CX2560 M4 CX2570 M4 Server Node Upgrade and Maintenance Manual FUJITSU Server PRIMERGY CX2550 M5 CX2560 M5 CX2570 M5 Server Node Upgrade and Maintenance Manual Available online D385x BIOS Setup Utility for FUJITSU Server CX2550 M4 CX2560 M4 CX2570 M4 Reference Manual D385x BIOS Setup Utility for FUJITSU Server CX2550 M5 CX2560 M5 CX2570 M5 Reference Manual Information on configurab...

Page 14: ...14 Operating Manual CX400 M4 Before you start ...

Page 15: ...able as a rack model Server enclosure The PRIMERGY CX400 M4 server enclosure consists of the server enclosure which has to be equipped with different configurations of server nodes as there are 4x PRIMERGY CX2550 M4 M5 or CX2560 M4 M5 server nodes 2x PRIMERGY CX2570 M4 M5 server nodes All server nodes are hot pluggable A mixture of CX2550 M4 M5 CX2560 M4 M5 and CX2570 M4 M5 nodes within the same s...

Page 16: ...g CX2550 M4 M5 server nodes the server enclosure can be equipped with up to 8x 2 5 inch HDD SSD modules Figure 1 Configuration with CX2550 M4 M5 server nodes Front overview with CX2560 M4 M5 server nodes Using CX2560 M4 M5 server nodes the server enclosure can be equipped with up to 24x 2 5 inch HDD SSD modules Figure 2 Configuration with CX2560 M4 M5 server nodes ...

Page 17: ...p to 12x 2 5 inch HDD SSD modules Figure 3 Configuration with CX2570 M4 M5 server nodes Pos Component 1 Operating panel for server node 1 2 Operating panel for server node 2 3 Operating panel for server node 3 4 Operating panel for server node 4 5 HDD bays for server node 1 6 HDD bays for server node 2 7 HDD bays for server node 3 8 HDD bays for server node 4 9 ID card ...

Page 18: ...view with CX2570 M4 M5 server nodes Figure 5 Configuration with CX2570 M4 M5 server nodes I If CX2570 M4 M5 GPU server nodes are installed only two installation bays are available bay 1 and bay 3 Pos Component 1 Installation bay 1 for server nodes 2 Installation bay 2 for server nodes 3 Installation bay 3 for server nodes 4 Installation bay 4 for server nodes 5 Installation bay 1 for PSU 6 Install...

Page 19: ...fer to the official configurator tool High level of availability and data security When memory data is accessed 1 bit errors are identified in the main memory and automatically corrected with the error correcting code ECC method ASR R Automatic Server Reconfiguration and Restart restarts the system in the event of an error and automatically hides the defective system components A RAID controller s...

Page 20: ...rs various options for protecting your data from unauthorized access By combining these options you can also achieve optimum protection for your system I A detailed description of the Security menu and how to assign passwords can be found in the D385x BIOS Setup Utility for FUJITSU Server PRIMERGY CX2550 M4 CX2560 M4 CX2570 M4 Reference Manual or D385x BIOS Setup Utility for FUJITSU Server PRIMERG...

Page 21: ...panel Figure 6 Controls on the front panel QRL left and right Pos Label Button Function 1 ID ID button Highlights the ID indicator on the front panel and I O panel for easy server identification 2 On Off button Used to switch the server on or off I If the system is running an ACPI compliant operating system pressing the On Off button will perform a graceful shutdown ...

Page 22: ...s Pos Label Indicator Status Description 1 PSU CSS indicator off No critical event detected CSS component orange on Prefailure event detected CSS component flashing orange CSS component failure detected 2 FAN CSS indicator off No critical event detected CSS component orange on Prefailure event detected CSS component flashing orange CSS component failure detected PSU FAN ...

Page 23: ...onent orange on Prefailure event detected non CSS component flashing orange Non CSS component failure detected Possible causes System is out of the specified temperature range Defective sensor CPU error Error detected by server management software 4 AC connected indicator green on The server enclosure is connected to the mains Pos Label Indicator Status Description ...

Page 24: ... Defective sensor CPU error Error detected by server management software 6 ID ID indicator see also iRMC related status signals on page 26 blue on The server has been highlighted using ServerView Operations Manager iRMC web interface or the ID button on the front panel for easy identification flashing blue The server has been highlighted for easy identification using the iRMC with disabled local V...

Page 25: ...ied time I After connecting the server to the mains it will take about 60 seconds until the server node will enter standby mode and can be switched on off The server is switched off and not connected to the mains The server is switched on and operating normally 9 CSS CSS indicator off No critical event detected CSS component orange on Prefailure event detected CSS component flashing orange CSS com...

Page 26: ... has been disabled during the remote session flashing blue flashing orange An emergency flash of the iRMC firmware is in progress I For more information on the emergency flash of the iRMC firmware see the FUJITSU Server PRIMERGY CX2550 M4 CX2560 M4 CX2570 M4 Server Node Upgrade and Maintenance Manual or FUJITSU Server PRIMERGY CX2550 M5 CX2560 M5 CX2570 M5 Server Node Upgrade and Maintenance Manua...

Page 27: ...nactive green on The HDD SSD being accessed 2 Error indicator off No HDD SSD error detected orange on An HDD SSD error has been detected Possible causes The drive is defective and needs replacing A RAID rebuild process has failed The HDD SSD module has not been inserted correctly flashing orange slowly HDD SSD RAID rebuild is in progress Data is being restored after replacing a drive that has been...

Page 28: ...ver nodes see the operating manuals of the relevant server nodes Pos Indicator Status Description 1 PSU status indicator flashing green The server is switched off but mains voltage is present standby mode green on The server is switched on and operating properly flashing orange An overload has been detected The PSU is still running but failure might be imminent orange on An PSU failure has been de...

Page 29: ...ct your sales outlet or our customer service team The actions described in this manual shall be performed by technical specialists A technical specialist is a person who is trained to install the server enclosure including hardware and software Repairs to the server enclosure that do not relate to CSS failures shall be performed by service personnel Please note that unauthorized interference with ...

Page 30: ...C or 45 C If the server enclosure is integrated into an installation that draws power from an industrial power supply network with an IEC309 connector the power supply s fuse protection must comply with the requirements for non industrial power supply networks for type A connectors The server enclosure automatically adjusts itself to a mains voltage see the type label of your server enclosure Ensu...

Page 31: ...ant instructions in this manual Never connect or disconnect data transmission lines during a storm risk of lightning hazard Make sure that no objects e g jewelry paperclips etc or liquids can get inside the server enclosure risk of electric shock short circuit In emergencies e g damaged casing controls or cables penetration of liquids or foreign bodies contact the server enclosure administrator or...

Page 32: ... before installing or removing internal options Do not damage or modify internal cables or internal devices Doing so may cause a server enclosure failure fire or electric shock and will void the warranty and exempt the manufacturer from all liability The circuit boards and soldered parts of internal options are exposed and can be damaged by static electricity To ensure reliable protection you must...

Page 33: ...ium Hg Mercury Pb Lead Working with optical disk drives and media When working with optical disk drives these instructions must be followed V CAUTION Only use CDs DVDs BDs that are in perfect condition in order to prevent data loss equipment damage and injury Check each CD DVD BD for damage cracks breakages etc before inserting it in the drive Note that any additional labels applied may change the...

Page 34: ... the center to the edge Do not use benzene thinners water record sprays antistatic agents or silicone impregnated cloth Be careful not to damage the CD DVD BD surface Keep the CDs DVDs BDs away from heat sources Do not bend or place heavy objects on CDs DVDs BDs Do not write with ballpoint pen or pencil on the label printed side Do not attach stickers or similar to the label side Doing so may caus...

Page 35: ...ass 1 V CAUTION The optical disk drive contains a light emitting diode LED which under certain circumstances produces a laser beam stronger than laser class 1 Looking directly at this beam is dangerous Never remove parts of the optical disk drive casing Modules with Electrostatic Sensitive Devices ESD modules Modules with electrostatic sensitive devices are identified by the following sticker Figu...

Page 36: ...ow to handle ESD modules see the relevant European or international standards EN 61340 5 1 ANSI ESD S20 20 Transporting the server enclosure V CAUTION Only transport the server enclosure in its original packaging or in packaging that protects it from impacts and jolts In Japan and APAC transporting the server enclosure in its original packaging does not apply Do not unpack the server enclosure unt...

Page 37: ...formation of the rack and the warning label If the server enclosure rack is intended for permanent connection to the mains only an authorized specialist electrician is allowed to work Please follow the regulation of each country If the server enclosure is integrated into an installation that draws power from an industrial power supply network with an IEC309 type connector the power supply s fuse p...

Page 38: ...g out measurement values including those relating to current energy consumption and air temperatures Either the Performance Monitor or the Task Manager can be used to read out CPU utilization levels The system complies with the requirements of European Regulations Find the CE declaration on certificate portal https sp ts fujitsu com sites certificates default aspx To open the CE declaration applic...

Page 39: ...ence will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between equipment and the receiver Connect...

Page 40: ...on should be switched off until they are needed as well as during long breaks and after completion of work Packaging information This packaging information does not apply in Japan and APAC Do not throw away the packaging You may need it later for transporting the server enclosure If possible the equipment should only be transported in its original packaging Information on handling consumables Plea...

Page 41: ...bles within Europe can also be found in the Returning used devices manual via your local Fujitsu branch or at http ts fujitsu com recycling The device must not be disposed of with domestic waste This device is labeled in compliance with European directive 2012 19 EU on waste electrical and electronic equipment WEEE This directive sets the framework for returning and recycling used equipment and is...

Page 42: ...42 Operating Manual CX400 M4 Important information ...

Page 43: ...at Make sure that the server enclosure is acclimatized for the time indicated in this table before putting it into operation In the table Acclimatization time the temperature difference refers to the difference between the operating environment temperature and the temperature to which the server enclosure was exposed previously outside transport or storage temperature Temperature difference C Mini...

Page 44: ...ction Documentation overview on page 11 print out the PDF files if required Ê Components that have been ordered additionally may be delivered loose with the server enclosure For mounting see the original component documentation Ê Install the server enclosure into the rack see section Installing removing the server enclosure in the rack on page 47 Ê Wire the server enclosure Follow the instructions...

Page 45: ... in the ServerView Suite Installation Manager user s guide on the Fujitsu manuals server under x86 Servers Software ServerView Suite Server Installation and Deployment Configuration information can also be found in the Operating Manual of the installed server node Local configuration and installation with or without the ServerView Installation Manager for further details see Operating Manual of th...

Page 46: ...e during transport Ê Check whether the items delivered match the details on the delivery note The product name and serial number of the product can be found on the identification rating plate It is located on the underside of the server enclosure at the front on the right Ê If the delivery is damaged or does not match the delivery note contact your supplier immediately Ê Notify your supplier immed...

Page 47: ...multaneously extended out of the rack there is a risk that the rack could tip over Fujitsu rack systems The rack systems from Fujitsu support the installation of PRIMERGY server enclosures PRIMECENTER rack PRIMECENTER M4 rack DataCenter rack 19 inch standard rack for Japan 19 inch slimline rack for Japan I For information on mounting the server enclosure in the rack see the mounting instructions p...

Page 48: ...r alignment feature to ensure that they can be adjusted to different rack depths Asymmetrical PRIMECENTER Rack and DataCenter Rack provide an enhanced cable management in the lateral rack area 3rd party racks I Installation in most current rack systems from other manufacturers 3rd party racks is also supported For details please contact your sales representative Wire the server enclosure Read the ...

Page 49: ...e in the rack Removing the inner rail from the carrier rails Ê Identify the inner rail and the outer rail Figure 11 Inner 2 and outer rail 1 Figure 12 Starting position of inner and outer rail Ê Push the lever 1 and pull the inner rail as far as possible towards the front side 2 ...

Page 50: ...urning outer rail Ê Turn the rails to the other side see arrow Figure 14 Removing inner rail from outer rail Ê Push the locking latch 1 and pull the outer rail as far as possible towards the front side 2 Now the inner rail is removed from the outer rail ...

Page 51: ...right carrier rail towards the server enclosure and position the holes onto the positioning screws 1 The carrier rail must lock in the corresponding hole Ê Push the carrier rail towards the front side until it locks into the supporting holes nicely 2 Figure 16 Fixing the carrier rail Ê Fasten the carrier rail with two M4 screws 3 Ê Repeat this procedure to install the left carrier rail ...

Page 52: ...er enclosure on the support uprights Ê Identify the right and the left rail Figure 17 Attaching the left carrier rail Figure 18 Adjusting the positioning clip Ê Move the left carrier rail towards the rear side 2 while holding the positioning clip 1 The mounting aid must lock in the corresponding holes Ê Release the positioning clip 1 after the designated position is reached ...

Page 53: ...olding the positioning clip 3 The mounting aid must lock in the corresponding hole Ê Release the positioning clip 5 after the designated position is reached Figure 19 Tightening the M5 screw Ê Tighten the M5 screw 6 on the front side of the rail Ê Repeat this procedure to install the right rail ...

Page 54: ...osure weighs more than 21 kg and is installed above the height of 25 U When using a lifter this removal procedure needs to be carried out by maintenance personnel For configurations below 32 kg At least two people are needed to lift the server enclosure out of the rack cabinet For configurations below 55 kg At least three people are needed to lift the server enclosure out of the rack cabinet For c...

Page 55: ... Mounting the server enclosure into the rack A Ê Set the back end of both inner rails 1 into the front entry of the both outer rails 2 Figure 21 Mounting the server enclosure into the rack A Ê Push the server enclosure as far as possible into the rack ...

Page 56: ...sure in the rack Ê When the server enclosure is stopped push the locking latch 1 on both sides and push the server enclosure in the rack 2 Figure 23 Mounting the server enclosure into the rack B Ê Push the server enclosure into the rack 1 until the locking mechanism engages ...

Page 57: ... at least two people are needed when server enclosure is installed in the height of 25U or more for Japan see 安全上のご注意 V Additionally a lifter is required in the following cases The server enclosure weighs more than 50 kg For configurations below 32 kg At least two people are needed to lift the server enclosure out of the rack cabinet For configurations below 55 kg At least three people are needed ...

Page 58: ...ove the height of 25 U When using a lifter this removal procedure needs to be carried out by maintenance personnel Figure 24 Removing the server enclosure out of the rack A Ê While pressing the locking levers 1 on both sides of the enclosure use the brackets 2 to pull the server enclosure out of its lock ...

Page 59: ...the server enclosure is stopped push the locking latch 1 on both sides and pull the server enclosure out of the rack 2 Figure 26 Removing the server enclosure out of the rack C Ê Pull out the chassis from the rack I Remove the server enclosure from the rack carefully Must be done with at least two people ...

Page 60: ...ing cables Ê Switch off the server and equipment switches Ê Disconnect all power cords from the properly grounded power outlets Ê Connect all cables to the server and peripherals Ê Connect all data communication cables into the utility sockets Ê Connect all power cords into the properly grounded power outlets Disconnecting cables Ê Switch off the server and equipment switches Ê Disconnect all powe...

Page 61: ...ically set to a mains voltage in the range 100 240 V You may only operate the server enclosure if its rated voltage range corresponds to the local mains voltage Ê Connect the power cord to the PSU Ê Connect the mains connector to an outlet on the socket strip of the rack I It will take about 60 seconds until the server can be switched on I For more information see the technical manual for the rack...

Page 62: ...vironment refer to Safety Precautions When operating the device outside of this operating environment the multi node server system may operate improperly damage data etc Furthermore Fujitsu cannot be held responsible for any related damage malfunction or loss of data etc Be sure to wait for 10 seconds or more after shutdown before turning the server node on After connecting the power cord press th...

Page 63: ...diately see chapter Technical data on page 77 The On Off button does not disconnect the server node from the mains voltage To completely disconnect it from the mains voltage remove the power plug s from the socket s Do not move strike or shake the multi node server system when it is turned on This can damage the hard disk in the server node and cause data loss Turn the multi node server system on ...

Page 64: ...y be prolonged and the screen may remain dark for several minutes Switching the server node off The power on indicator lights up green Ê Shut down the operating system properly The server node is switched off automatically and enters standby mode The AC connected indicator lights up green I If the operating system does not turn off the server automatically press the On Off button for at least four...

Page 65: ... be lost iRMC iRMC offers various options for switching the server on and off e g via the System power button on the Global icons of the iRMC web interface V CAUTION when switching off the power The operation of the power switch can be specified as Do Nothing Stand by Hibernate and Shutdown depending on the OS settings The default is Shutdown On the server node functions corresponding to Stand by ...

Page 66: ...een locking clips 1 and open the locking lever 2 Ê Pull the HDD SSD module out a few centimeters 3 Ê Wait about 30 seconds to allow the HDD to spin down I This is not necessary when removing an SSD I This period is necessary for the RAID controller to recognize that an HDD module has been removed and for the HDD to come to a stop Ê Pull the HDD SSD module completely out of its bay ...

Page 67: ...odule is not replaced immediately always replace a dummy module into the unused HDD SSD bay to comply with applicable EMC regulations and satisfy cooling requirements Figure 28 Installing a 2 5 inch dummy module Ê Push the dummy module into the empty bay until it engages The HDD SSD module is installed in the reverse order ...

Page 68: ...ion of the arrow 1 Ê Press in on the green locking latch 2 Ê While keeping the green locking latch pressed pull the PSU out of its bay 3 V CAUTION Never leave the bay for the hot plug PSU empty for more than two minutes during operation Otherwise excessive temperatures could damage system components The hot plug PSU is in installed in the reverse order ...

Page 69: ...the meantime all remaining server nodes run in throttling mode with reduced performance V CAUTION Follow the safety instructions in the chapter Important information on page 29 Figure 30 Removing the server node dummy module Ê Undo the locking mechanism 1 of the release lever and pull the server node dummy module out of the bay 2 6 4 2 Installing the CX2550 M4 M5 or CX2560 M4 M5 server node V CAUT...

Page 70: ...d removing the tubes from the node check that the LC flexible tubes riser is not off as shown I Only necessary for CX2550 M4 and CX2560 M4 server nodes Ê Remove the gasket of the lower server node and keep it for later use Ê Push the server node at the handle into the server enclosure until the locking mechanism snaps into place I Only necessary for CX2550 M4 and CX2560 M4 server nodes Ê Install t...

Page 71: ...CX400 M4 Operating Manual 71 Operation This is the good case This is the bad case gap under the bracket ...

Page 72: ...nstructions in the chapter Important information on page 29 Figure 31 Installing the server node Ê Push the server node at the handle into the server enclosure until the locking mechanism snaps into place Ê If applicable connect all external cables to the server node The server node is removed in the reverse order ...

Page 73: ...at contain abrasives or may corrode plastic Ensure that no liquid enters the system Ensure that the ventilation areas of the server enclosure and the monitor are clear Do not use any cleaning sprays including flammable types It may cause a device failure or a fire Clean the keyboard and the mouse with a disinfecting cloth Wipe the server enclosure and monitor casing with a dry cloth If particularl...

Page 74: ...74 Operating Manual CX400 M4 Operation ...

Page 75: ...e a list of any error messages that were displayed Ê Switch off the server Ê Contact our customer service team I The meaning of the error message is explained in the documentation for the relevant components and programs available online at http manuals ts fujitsu com Power on indicator remains unlit after you have switched on your device Cause Troubleshooting Power cable incorrectly connected Ê E...

Page 76: ...ed when the system was switched off Ê Reconfigure the RAID controller for the drive using the corresponding utility Information is provided in the documentation for the RAID controller or Ê Remove and reinstall the drive while the system is switched on If the HDD SSD continues to be shown as defective then replace it see the FUJITSU Server PRIMERGY CX400 M4 Server Enclosure Upgrade and Maintenance...

Page 77: ...s primergy For more information see the Documents tab under for example Rack Servers For Japan http www fujitsu com jp products computing servers primergy Server enclosure Server nodes Server enclosure type 2U chassis for 19 inch rack Rear bays 4 bays for half wide server nodes and 2 bays for PSU Fan configuration 8x hot pluggable fans Power supply configuration 2x hot plug PSUs Product Model Name...

Page 78: ...r of storage drives max 2x 2 5 inch applicable to CX2550 or 6x 2 5 inch applicable to CX2560 6x 2 5 inch Slots up to 2 PCI cards or 1 OCP card up to 1 PCI card 1 OCP card or up to 4 SXM2 modules Server enclosure W x D x H Body 444 0 x 885 8 x 87 6 mm Bezel 480 2 x 885 8 x 87 6 mm Mounting depth server enclosure 850 0 mm Height server enclosure 2 U Mounting cable depth server enclosure 200 mm 1000 ...

Page 79: ...10 C 35 C without ATD The maximum temperature depends on type of the CPU Transport 2K2 25 C 60 C Humidity 10 85 non condensing Condensation during operation must be avoided Sound power level LWAd ISO 9296 7 0 B standby 7 7 B operation Sound pressure level LpAm ISO 9296 57 0 dB standby 63 8 dB operation Rated voltage range 100 240 V Frequency 50 Hz 60 Hz Max rated current 10 5 A 9 2 A 100 V 240 V R...

Page 80: ...stralia New Zealand RCM CB IEC60950 1 AS NZS Deviations Saudi Arabia SASO CB IEC 60950 1 Kenia KEBS KS Kenya Standards CB IEC 60950 1 Kuwait KUKAS KSS Kuwaiti Standards Specifications CB IEC 60950 1 Tanzania TBS CB IEC 60950 1 Electromagnetic compatibility International CISPR 22 Europe EN 55032 Class A EN 55024 EN 61000 3 2 EN 61000 3 3 ETSI 300386 USA Canada 47CFR part 15 Class A ICES 003 Taiwan ...

Page 81: ...A CISPR 22 This device can cause radio interference in residential areas Korea KN 32 KN 35 CE marking to EU directives Electromagnetic compatibility 2014 30 EU Low Voltage Directive 2014 35 EU Restriction of hazardous substances 2011 65 EC RoHS Compliance EU EN 50581 RoHS Compliance Taiwan CNS 15336 ...

Page 82: ...82 Operating Manual CX400 M4 Technical data ...

Page 83: ...http manuals ts fujitsu com under x86 Servers Safety Eco Warranty For Japan http www fujitsu com jp products computing servers primergy support For the warranty regulations select 製品保証ご案内 無償修理期間 Service Telephone numbers of the local service partner can be found online at http ts fujitsu com support servicedesk html ...

Page 84: ...84 Bearbeitungsstand Bestellnummer Warranty and service ...

Reviews: