200
Upgrade and Maintenance Manual
RX2540 M2
Hard disk drives (HDD) and solid state drives (SSD)
7.4.3.4
Concluding steps
Ê
Refer to the RAID documentation configuring the RAID, see
.
7.4.4
Replacing a 2.5-inch HDD/SSD module
V
CAUTION!
●
Only remove an HDD/SSD module during operation if the drive is not
currently being accessed. Observe the indicators on the HDD
module, as described in the operating manual of your server.
●
An HDD/SSD module can be replaced while the system is in
operation.
RAID configuration with a RAID controller:
Only RAID level 1, 1E, 10, 5, 50, 6 or 60 is allowed.
RAID configuration without a RAID controller:
Please follow the instruction provided separately.
●
All HDD/SSD modules (drives) must be uniquely identified so that
they can be reinstalled in their original mounting locations later. If this
is not done, existing data can be lost.
7.4.4.1
Preliminary steps
Ê
"Locating the defective server" on page 61
Ê
Locate the defective HDD/SSD module as described in section
diagnostic indicators on the front" on page 63
.
Only applicable for removing intact HDD/SSD modules:
Ê
Before removing a non-defective HDD/SSD module, put the drive into
"Offline" mode using your RAID configuration software.
Customer Replaceable Unit
(CRU)
Hardware: 5 minutes
Tools:
tool-less
Summary of Contents for PRIMERGY RX2540 M2
Page 6: ...Upgrade and Maintenance Manual RX2540 M2 ...
Page 48: ...48 Upgrade and Maintenance Manual RX2540 M2 Before you start ...
Page 128: ...128 Upgrade and Maintenance Manual RX2540 M2 Basic software procedures ...
Page 142: ...142 Upgrade and Maintenance Manual RX2540 M2 Power supply unit PSU ...
Page 392: ...392 Upgrade and Maintenance Manual RX2540 M2 Processor CPU ...
Page 452: ...452 Upgrade and Maintenance Manual RX2540 M2 Accessible drives ...
Page 558: ...558 Upgrade and Maintenance Manual RX2540 M2 System board and components ...
Page 602: ...602 Upgrade and Maintenance Manual RX2540 M2 Appendix ...