RX2540 M2
Upgrade and Maintenance Manual
307
Expansion cards and backup units
8.6.4
Removing a GPGPU card in riser module 2
8.6.4.1
Preliminary steps
Ê
If applicable,
"Locating the defective server" on page 61
Ê
"Suspending BitLocker functionality" on page 95
Ê
"Shutting down the server" on page 65
Ê
If applicable, remove all external cables from the expansion card to be
removed.
I
If there is a cable installed to an expansion card in the upper slot, see
section
"Note for installation with expansion cards in slot 5 and slot
Ê
"Disconnecting the power cord" on page 66
Ê
"Getting access to the component" on page 68
Ê
If applicable, disconnect internal cables from the GPGPU card.
8.6.4.2
Removing the FBU
Ê
If applicable, remove the FBU as described in section
8.6.4.3
Removing the riser module 2
Ê
Remove the riser module 2as described in section
.
Upgrade and Repair Unit
(URU)
Hardware: 5 minutes
Software: 5 minutes
Tools:
Phillips PH2 / (+) No. 2 screw driver / nut driver 5 mm
Summary of Contents for PRIMERGY RX2540 M2
Page 6: ...Upgrade and Maintenance Manual RX2540 M2 ...
Page 48: ...48 Upgrade and Maintenance Manual RX2540 M2 Before you start ...
Page 128: ...128 Upgrade and Maintenance Manual RX2540 M2 Basic software procedures ...
Page 142: ...142 Upgrade and Maintenance Manual RX2540 M2 Power supply unit PSU ...
Page 392: ...392 Upgrade and Maintenance Manual RX2540 M2 Processor CPU ...
Page 452: ...452 Upgrade and Maintenance Manual RX2540 M2 Accessible drives ...
Page 558: ...558 Upgrade and Maintenance Manual RX2540 M2 System board and components ...
Page 602: ...602 Upgrade and Maintenance Manual RX2540 M2 Appendix ...