Chapter 25
Addition, Deletion, and Upgrade of FRU
25-5
25.2.1
Active Deletion
First, select a unit to be deleted as described below.
1. Log in to the XSCF.
2. Execute the deletion command (
deletefru
).
3. When the following deletion menu is displayed, select the type of FRU to be deleted.
FIGURE 25-2
Initial Page of the Maintenance Menu
Note –
The display may vary depending on the XCP version.
Perform the operation according to the instructions displayed in the deletion menu. For
details, see the appropriate chapter on FRU replacement.
25.2.2
Cold Deletion
In cold deletion the main line switches of the system are turned off and the deletion menu is
not available. Perform the deletion according to the following steps.
1. Set the mode switch on the operator panel to Service.
2. Use one of the following methods to stop (power off) all domains at once.
■
Press and hold the POWER switch on the operator panel for at least four seconds.
■
From a console that is connected to XSCF, log in to XSCF, and execute the
poweroff -a
command.
3. Switch off all main line switches for the AC section (ACS) in the power supply
system.
4. Delete the FRUs.
Perform the same operation as the removal steps of a FRU replacement. For details, see
the appropriate chapter on FRU replacement.
XSCF>
deletefru
---------------------------------------------------
Maintenance/Removal (Deletion) Menu
Please select a type of FRU to be removed (deleted).
1. CMU/IOU (CPU Memory Board Unit/IO Unit)
---------------------------------------------------
Select [1|c:cancel]:
Summary of Contents for SPARC Enterprise M8000
Page 4: ......
Page 15: ...Contents xv Index Index 1 ...
Page 16: ...xvi SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 22: ......
Page 27: ...Chapter 1 Safety and Tools 1 5 M9000 Server Front View ...
Page 29: ...Chapter 1 Safety and Tools 1 7 Power Supply Unit PSU ...
Page 38: ...1 16 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 88: ...2 50 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 148: ......
Page 154: ...5 6 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 205: ...Chapter 7 I O Unit IOU Replacement 7 13 FIGURE 7 8 Removing the IOU Front of M9000 1 1 2 3 ...
Page 227: ...Chapter 8 FAN Unit Replacement 8 11 FIGURE 8 9 Removing the FAN Unit Rear of M8000 1 2 ...
Page 256: ...10 8 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 272: ...11 16 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 312: ...13 30 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 340: ...15 14 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 358: ...17 10 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 370: ...18 12 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 380: ...19 10 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 409: ...Chapter 20 Backplane Replacement 20 29 FIGURE 20 16 Removing the FANBP Rear of the M8000 ...
Page 422: ...21 10 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 439: ...Chapter 23 Switch Backplane Replacement 23 7 FIGURE 23 4 Removing the SWBP Rear of the M8000 ...
Page 442: ...23 10 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 460: ...24 18 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 484: ...25 24 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 494: ...A 10 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 544: ...C 4 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...
Page 552: ...D 8 SPARC Enterprise M8000 M9000 Servers Service Manual October 2012 ...