3-26
"Grounding for Three-phase Power Supply" in Section 3.3.5,
"Grounding"
"This server allows the use of grounding wire with another
grounding wire for shared grounding; however, the grounding
methods may vary by the building where the system is
installed. Check the related standards in order to use the correct
grounding method. When using shared grounding, the
grounding resistance must not be greater than 10
Ω
. Make sure
that the facility administrator or a qualified electrical engineer
verifies the grounding method for the building and performs
the grounding work." should be substituted with the following
description:
The grounding resistance must not be greater than 10
Ω
. The
grounding method varies by the building where you install the
server. Make sure that the facility administrator or a qualified
electrical engineer verifies the grounding method for the
building and performs the grounding work.
3-26
"CPU Types and Server Maximum Power Consumption" in
Section 3.3.6 will be corrected. See
Maximum Power Consumption” on page 24
for detail.
SPARC Enterprise
M8000/M9000 Servers
Overview Guide
1-11
TABLE 1-3 "Power consumption Examples," in Section 1.2.2,
"Power Specifications" will be corrected. See
for detail.
3-6
"Airflow Indicator" in Section 3.2.2.7
"Note - Airflow monitoring measurement values are for
reference only." should be substituted with the following
description:
"Note - The
showenvironment air
command displays the
calculated airflow based on the fan speed such as Low speed or
High speed etc. The fan speed is displayed by
showenvironment Fan
command."
SPARC Enterprise
M8000/M9000 Servers
Service Manual
To insert or remove a FRU which allows hot replacement or hot
addition, you must use the antistatic wrist strap and properly
attach the band of the wrist strap to one of your wrists to
remove the static of FRU in advance. See
for detail.
TABLE 3
Hardware Documentation Updates
(Continued)
Title
Page Number
Update
Summary of Contents for SPARC Enterprise M8000
Page 4: ......
Page 8: ...viii SPARC Enterprise M8000 M9000 Servers Product Notes for XCP Version 1092 April 2010 ...
Page 12: ...xii SPARC Enterprise M8000 M9000 Servers Product Notes for XCP Version 1092 April 2010 ...
Page 88: ...76 SPARC Enterprise M8000 M9000 Servers Product Notes for XCP Version 1092 April 2010 ...