En-16
8.2. Dip switch setting
(1) Capacity settings of indoor units to be controlled
The capacity of indoor units to be controlled is set.
Indoor unit
capacity
Dip switch setting (*: factory setting)
SET1-1
SET1-2
SET1-3
SET1-4
SET2-1
5.0 kW *
ON
OFF
ON
OFF
OFF
6.3 kW
ON
OFF
ON
OFF
ON
8.0 kW
ON
ON
ON
OFF
OFF
10.0 kW
OFF
ON
ON
OFF
ON
12.5 kW
OFF
ON
OFF
ON
OFF
14.0 kW
ON
ON
OFF
ON
OFF
20.0 kW
ON
OFF
ON
ON
OFF
25.0 kW
OFF
ON
ON
ON
OFF
40.0 kW
ON
OFF
OFF
ON
ON
50.0 kW
OFF
ON
OFF
ON
ON
Not described
above
Settings prohibited
(2) Setting digital input signal methods
• Select either edge method or pulse method as the external inputs signal method.
DIP switch SET2-2
Digital input signals format
OFF (factory setting)
Edge
ON
Pulse
Make sure that SET2-3 and SET2-4 are always OFF.
(3) Analog external inputs method
• You can select the item to be controlled using analog external inputs from the external
controller (either “Operation temperature” or “Required operation performance”).
• Make the DIP switch SET3-1 settings before making the SET3-2 settings.
• Make sure to set a connection status that uses the external controller.
• If SET3-1 is ON, VRF device controls will be disabled.
(i) Analog external inputs ON/OFF
DIP switch SET3-1
Analog external inputs ON/OFF
OFF (factory setting)
OFF
ON
ON
(ii) Control items
• The items to be controlled are selected according to the device status that uses the
external controller.
DIP switch SET3-2
Control conditions
OFF (factory setting)
Operation temperature
ON
Required operation performance
(4) AC (air conditioning.) control settings
• Select the AC control format from either “outlet temperature control” or “inlet temperature
control”.
DIP switch SET3-3
Temperature control position
OFF (factory setting)
Outlet temperature control
ON
Inlet temperature control
Make sure that SET3-4 is always OFF.
(5) RB unit bypass circuit feasibility
• If connecting the RB unit and a general indoor unit 1-to-1 in the heat recovery system
unit, con
fi
gure a bypass circuit in the RB unit when the heat thermostat is OFF.
• Prevents hot air from outlet when the heat thermostat is OFF.
• If the indoor unit is 40kW or 50kW type, the RB unit cannot be connected.
DIP switch SET4-3
OFF (factory setting)
No bypass
ON
With bypass
(6) Administrative indoor unit setting
• You can set the DX-kit as the “administrative indoor unit” from among multiple indoor
units (including the DX-kit) connected using the same refrigerant system (or RB unit).
• Only one administrative indoor unit can be set using the same refrigerant system (or RB
unit).
If forming the remote controller group,set this DIP switch "OFF".
DIP switch SET4-4
Administrative indoor unit settings
OFF (factory setting)
OFF
ON
ON
• Precautions if using the DX-kit as the administrative indoor unit
If the ”Administrative indoor unit setting”is “ON” for another indoor unit connected to the
same refrigerant system (or RB unit), make sure to turn ”OFF” that setting. For details, see
the wired remote controller installation manual.
• When connecting the wired remote controller to the DX-kit, set this switch to OFF. (Set
the “Administrative indoor unit setting” with the wired remote controller.)
Make sure to set SET4-1 and SET4-2 to always OFF.
(7) Remote controller selections
The cable type of wired remote controller has been selected.
DIP switch SW1
Wired remote controller cable type
2WIRE (factory setting)
2 wire type
3WIRE
3 wire type
8.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “8.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter
indicator
interval
11
00
Standard
○
Adjust the
fi
lter cleaning interval noti
fi
-
cation. If the noti
fi
cation is too early,
change to setting 01. If the noti
fi
cation
is too late, change to setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the
fi
lter indicator.
Setting 02 is for use with a central
remote controller.
01
Disable
02
Display only on
central remote
controller
Auto
restart
40
00
Enable
Enable or disable automatic system
restart after a power outage.
01
Disable
○
Cool Air
Prevention
43
00
Super low
Restrain the cold air
fl
ow with making
the air
fl
ow lower when starting
heating operation.
If using Outlet temperature control
(DIP switch SET3-3: OFF) , set this
function"01".
01
Follow the
setting on
the remote
controller
○
Error report
target
47
00
All
○
Change the target for reporting errors.
Errors can either be reported in all lo-
cations, or only on the central remote
controller.
01
Display only on
central remote
controller
Switching
functions
for external
inputs and
external
outputs
terminals
60
00
Mode 0
○
The connection terminal functions can
be changed depending on the type
of external device. For details of the
connection terminal functions, see the
Design & Technical Manual.
01
Mode 1
Selecting
stop
operation
during an
external
error
64
00
Mode 0
○
Thermostat off
01
Mode 1
Thermostat OFF + fan stop
02
Mode 2
Thermostat OFF + fan stop + outdoor
unit stop
9381279005_IM.indb 16
9381279005_IM.indb 16
6/30/2014 11:31:18 AM
6/30/2014 11:31:18 AM