Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Indoor unit
individual
operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Judgement standard
Check
Check contents
Procedure
These are representative figures of AJ*108LELAH at the standard condition. ( Indoor : 27°C,
Outdoor : 35°C )
If conditions are different from those above mentioned, the figures will be changed slightly.
It depends on following conditions.
Outdoor unit capacity
Indoor and outdoor temperature
Indoor unit capacity
Pipe length
etc
<Indoor unit service tool + actual measurement>
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and
check the description of the Error code.
< Refer to the Trouble shooting in the Service manual.>
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not
Evaporator Icing up protection, High discharge temperature protection,etc.
< Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit
Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc.
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
< Refer to the regulation of installation in the Installation manual>
Trouble shooting on Test run operation
01-05
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...