SWITCH POSITION
SW107
SW108
SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105
LED104
LED102
(RED)
ERROR
Push button switch
7 Segment
LED Lamp
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit
Main PCB is set to “00”. If it is not set to “00”,
it means the address of that device is not set.
(Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed
on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons
on the outdoor unit Main PCB to configure settings
according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
M
SELECT
SELECT
ENTER
1-2-4 Automatic address setting for Indoor units
It may take about 10 minutes for completing the processing.
End
First 2 digits Last 2 digits
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
Automatic address setting
for indoor units
The number of indoor units with normal settings will be displayed at the first 2 digits of
the 7 segment display.
The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
ENTER
SELECT
ENTER
Error
Found
01-07
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...