Trouble shooting 64
OUTDOOR UNIT Error Method:
High Pressure Protection 1
Indicate or Display:
Detective Actuators:
Detective details:
1. 3-way valve not opened 2. Outdoor unit fan operation defective, foreign matter at heat
exchanger, excessive ambient temperature rise 3. Check valve clogged
4. EEV defective, strainer clogged 5. Solenoid valve defective
6. High pressure switch 1 defective 7. Refrigerant overcharged
High pressure switch 1
"Protection stop by "high pressure switch 1 operated during compressor 1
operation"" generated 3 times within 60 minutes
EEV operation check
Check of strainers before and after EEV
EEV(EEV 1) open?
Strainer clogging check. (before EEV)
Refer to "Service Parts Information 9".
Refer to "Service Parts Information 8".
Check Point 2 : Check the EEV, strainer (indoor unit)
No foreign matter in air passage?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by effect of other heat sources?
Discharged air not sucked in?
Check Point 2 : Check the outdoor unit fan operation,
heat exchanger, ambient temperature
High pressure switch 1 characteristics check
* For the characteristics of the high pressure switch 1, refer to "Service Parts Information 16".
Check Point 4 : Check high pressure switch 1
Check Point 5: Check the refrigerant amount
Refrigerant charged amount check
Check Point 3-2 : Check the check valve
Check if check valve (oilseparetor (out) of compressor 1)
is not clogged.
Check Point 3-1 : Check the EEV, strainer
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A4. 2
Error Code
: A4
<Cooling operation>
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
K
O
K
O
OK
OK
OK
OK
OK
Forecast of Cause :
E. A4. 2
04-72
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...