Trouble shooting 68
Outdoor Unit - No Power
Check Point 3 : Check Electrical Components
If the symptom does not change by above Check 3, replace Main PCB or Filter PCB
OK
OK
NO
Check the voltage of power supply.
>> Check if the reted voltage appears at Outdoor Unit Terminal L1, L3 - N.
AC
Forecast of Cause :
1. Power Supply failure 2. Outside cause 3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isnt the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to
Installation Manual or Data & Technical Manual.
Check Point 2 : Check Outside Cause such as Voltage drop or Noise
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may
cause harmonic wave).
Check the complete insulation of grounding.
Check the fuse on the Filter PCB.
OK
Replace the fuse.
Recheck if the power supply terminals section is shorted.
(Note) Always check in the power off state.
NG
NG
Disconnect connecting cable of the Filter PCB and Main PCB and recheck.
if the power supply terminals section is not shorted.
(Note) Always check in the power off state.
OK
NG
Check If the FAN motor PCB has a
damage or not. ( Check short circuit )
Replace the Filter PCB.
NG
OK
Check if the circuit between pin No. 1 and pin No.4 of CN104/ CN122 on
the Main PCB (8, 10HP) / between pin No. 1 and pin No.3 of CN 701 on
the FAN Driver PCB(12HP) are not short-circuit (Short - NG)
* Disconnect FAN motor when check the circuit
NG
Replace the FAN Motor
NG
04-76
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...