Forecast of Cause:
1.
Indoor unit Controller PCB
failure
2. Wireless LAN adapter PCB failure
3. Wiring connection failure
Wireless LAN adapter Non-Energized
Trouble shooting 101
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Indicate of Display:
Indoor Unit :
Operation lamp: 1 time Flash
Timer lamp : 8 time Flash
ERROR CODE : [ 18 ]
Wireless LAN adapter :
LED 1 (Green) : OFF
LED 2 (Orange) : OFF
Indoor unit Controller PCB
Wireless LAN adapter PCB
When the does not output the DC12 voltage from Controller PCB.
NO
Check Point 1 : Cheak the Sleep mode
Press the Wireless LAN adapter setting button the 3 seconds or more.
OK
Check Point 2 : Cheak the connection
Check any loose or removed connection of between the Wireless LAN adapter PCB and Controller PCB
>If there is abnormal condition, correct it.
Check the connection condition on the Controller PCB
>If there is loose connector, open cable or miswiring, correct it.
Check Point 3 : Cheak the
Wireless LAN adapter PCB and Controller PCB
Check Voltage at CN12 (terminal 1-2) of Controller PCB.
>If it is DC 0V, Controller PCB is failure.
Replace Controller PCB.
>If it is DC12V, Wireless LAN adapter PCB failure.
Replace Wireless LAN adapter and please cancel the air conditioner of the registration on the Mobile App.
After the replace adapter, Please perform the pairing on the App.
Wireless LAN adapter : LED 1 (Green) : Flashing Fast , LED 2 (Orange) : Flashing Fast
Did the display pattern will change?
YES
Refer To “Trouble shooting 98 ”
>> Refer to “ Air conditioning unregistration method”
>> Refer to “ Air conditioner registration Paring Method”
04-110
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...