2-1 INPUT / OUTPUT LIST
2. OUTDOOR UNIT
02-01
Input / output or kind of detail
Control range
Discharge pressure sensor <HIGH> Pressure sensor
Measure range 0.0 to 5.0MPa
Suction pressure sensor <LOW> Pressure sensor
Measure range 0.0 to 1.7MPa
Discharge temperature sensor <TH1> Themistor <Blue> Measure range 10 to 130
Heat exchanger temperature sensor <TH5> Themistor
<
> Measure range -35 to 70
Sub-cool heat exchanger (outlet) sensor<TH9> Themistor
< White> Measure range -35 to 70
Liquid temperature sensor <TH7> Themistor
<Green> Measure range -35 to 70
Suction temperature sensor <TH4> Themistor
<Red>
Measure range -35 to 70
Outdoor temperature sensor <TH3> Themistor
< - > Measure range -25 to 58
Operation current sensor
Current sensor
Rotary SW & DIP-SW & Push SW
Electronic expansion valve 1 (Main)
EEV coil
Operating voltage DC12V
Electronic expansion valve 2 (SC-Hex)
EEV coil
Operating voltage DC12V
4-way valve
4-way valve coil
AC220-240V, 50/60Hz 6/5 W
Crank case heater
For Inverter Compressor
AC240V, 35W
Base heater
Field supply
AC220-240V, 35W
LON WORKS
Inverter communication
External input 1 (CN131)
(Low noise mode operation)
External input 2 (CN132)
(Cooling / Heating priority)
External input 3 (CN133)
(Outdoor unit operation peak control)
External input 4 (CN134)
(Emergency stop operation)
Dry contact input
Single LED 101
Single LED 102
LED display
Address and function setting
Display the information on operation, error and setting with single LED and
7 segment LED.
Control output: DC 0/12-24V, Max.30mA
Control output: DC 0/12-24V, Max.30mA
External output 1 (CN136) (Error display)
External output 2 (CN137) (Operation display)
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Communication
Input / Output
External
Input / Output
I
N
P
U
T
O
U
T
P
U
T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Pressure switch
Pressure switch
Open 4.2MPa Short 3.2MPa
Fan motor 1 (Upper)
DC Brushless motor
7 Segment LED
Compressor
Indoor unit Outdoor unit
Fan motor 2 (Lower)
DC Brushless motor
DC Inverter compressor
Brown
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...