2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
During the oil recovery operation, appears on the display of wired and central remote controller,
and appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
Others
02-08
<
Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition >
30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg" or 6 minutes
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
3. Oil Recovery in Heating operation
1. Oil Recovery in Cooling operation
<
Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition >
After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode)
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
<
Start condition >
LP < 0.13Mpa
< End condition >
HP- LP 0.7Mpa and LP 0.18Mpa or LP 0.52Mpa or 15 minutes have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
2. Oil Recovery in Cooling start-up operation
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...