02-11
Protective Function Detect Parts
Operating Condition
Operation
Low Pressure
Protection 1
Low Pressure
Sensor
COOL HEAT
High Pressure
Protection Stop 1
High Pressure
Sensor
<Pattern starting condition>
High-pressure 4.00MPa
<Pattern reset condition>
5 minutes have elapsed and high-pressure 3.50MPa
Compressor stopped
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition>
Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition>
5 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
High Pressure
Protection Stop 2
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
Error display
<Starting conditions>
3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly
(450pls)
Abnormal Low
Pressure Protection
Control
Low Pressure
Sensor
<Starting condition>
Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure
Protection Stop
Low Pressure
Sensor
<Pattern starting condition>
Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition>
3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition>
Pattern generated 5 times within 180 minutes.
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor stopped
(permanent stop)
Error display
<Reset condition>
3 minutes have elapsed and
low-pressure 0.18MPa
Compressor stopped
DISPLAY
Compressor Temp
Protection Stop
Compressor
Temp
Thermistor
<Pattern starting condition>
Compressor temperature fixed value (130°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 90°C
Compressor stopped
Compressor stopped
(permanent stop)
Error display
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
P2
EA41
EA31
EA42
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise
.
P2
Compressor stopped
Compressor Temp
Protection
Compressor
Temp
Thermistor
Compressor temperature fixed value (115°C)
Compressor stopped
<Starting condition>
<Reset condition>
Compressor temperature
<
fixed value (110°C)
Discharge temperature
<
fixed value (105°C)
and
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...