Trouble shooting 14 E32. 1
INDOOR UNIT Error Method:
Indoor unit PCB Model Information
Error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
3 continuous failure of lead test of EEPROM at Power ON, or Apparent Model
information error from EEPROM. Also, Error on Model information upon model
information test of EEPROM, or Model information of EEPROM not possible to
recover.
Forecast of Cause :
1. Outside cause 2. Connection failure of electric components 3. Controller PCB defective
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 :
Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a non-
volatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
04-22
Summary of Contents for UTP-VX30A
Page 1: ...SERVICE MANUAL ...
Page 5: ...1 TEST RUN ...
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 40: ...3 INDOOR UNIT OPERATION ...
Page 70: ...4 TROUBLE SHOOTING ...
Page 205: ...5 APPENDING DATA ...
Page 210: ...05 04 1 MODELS AUXK018 024 030 034 036 045 054GLAH AUXM018 024 030GLAH CASSETTE TYPE ...
Page 214: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 217: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 218: ...05 10 1 MODELS ARXK04 07 09 12 14 18 24GCLH COMPACT SLIM DUCT TYPE ...
Page 219: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 220: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 222: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 223: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 224: ...05 15 1 MODELS ASYA004 007 009GTAH ASHA004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV internal ...
Page 225: ...05 15 2 MODELS ASYE004 007 009GTAH ASHE004 007 009GTAH COMPACT WALL MOUNTED TYPE EEV external ...
Page 227: ...05 15 4 MODELS ASYA030 034GTAH ASHA030 034GTAH ...
Page 230: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 231: ...05 17 MODEL ARXH096GTAH ...
Page 232: ...MODELS AJ 072LELAH AJ 090LELAH UNITS 5 2 2 Outdoor Unit 05 18 ...
Page 233: ...MODEL AJ 108LELAH OUTDOOR 05 19 ...
Page 240: ...6 DISASSEMBLY PROCESS ...