Line
Function
Setting range or display
Setting
increment
Basic setting
923
S
Flow temp setp min OT 25°C
6... 35 °C
0,5 °C
18 °C
The lowest starting temperature for cooling for an outdoor temperature of 25 °C.
924
S
Flow temp setp min OT 35°C
6... 35 °C
0,5 °C
18 °C
The lowest starting temperature for cooling for an outdoor temperature of 35°C.
928
S
Room influence
--, 1... 100 %
1 %
80 %
If the installation is fitted with an room sensor :
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
932
S
Room temp limitation
--, 0,5... 4 °C
0,5 °C
0,5 °C
938
S
Mixing valve decrease
0... 20 °C
1 °C
0 °C
941
S
Actuator running time
30... 873 s
1 s
240 s
945
S
Mixing valve in heating mode
Control, Open
Control
946
S
Lock time dewpoint limiter
--, 10... 600 min
10 min
60 min
947
S
Flow temp setp incr hygro
--, 1... 20 °C
1 °C
10 °C
948
S
Flow setp incr start at r.h.
0... 100 %
1 %
60 %
950
S
Flow temp diff dewpoint
--, 0... 5 °C
1 °C
2 °C
963
S
With prim contr / system pump
No, Yes
No
969
S
Operating mode changeover
No, Off, Automatic
Off
30
20
18
16
°C
°C
25
35
908
909
923
924
Flow temperature setpoint
Outside temperature
Flow temperature setpoint
(
with
minimum limit)
Flow temperature setpoint
(
without
minimum limit)
figure 18 - Limitations on the
startingtemperature setting
Geographical area
Water start
temperature limit
(line 923 & 924)
Internal area
18°C
Coastal area (width 30 km)
19°C
Coastal area (width 50 km)
20°C
Coastal area (width 50 km)
21°C
Coastal area (width 50 km)
22°C
1
2
3
4
5
figure 19 - Water start temperature limit
The water temperature must be restricted to a value set according to the geographical area. Setting to the lowest temperatures
runs the risk of causing condensation on the floor, together with all the other risks this may engender.
If the limit temperatures are not observed, the manufacturer may not be held responsible for any physical injuries or damage
to equipment that may be caused.
Installation and operating manual "1395 - EN"
- 21 -
Control Box