XG0440DC/XG0440DCR Hardware Guide
Chapter 2 Installation
Requirements for Installation Environment
28
2.1 Requirements for Installation
Environment
Before installing the switch, please check the following:
•
Make sure that the switch and all the other options shown in this document are available for installation.
•
All the cables comply with the specifications of the interface connectors.
Warning
Do not connect cables to interface connectors other than those compatible with the connector's
specifications.
Install the product under the following environmental conditions.
2.1.1
Installation Requirements
Caution
Install the product under the following conditions. Using the product outside the required
environment may cause failure of the product.
Temperature and Humidity Requirements
Power Requirements
Reference
Temperature (degrees C)
Humidity (%RH)
Operation
0 to 40
15 to 85
Non-operation
0 to 50
8 to 90
Item
Requirements
Voltage
AC90V-264V
Frequency
50Hz / 60Hz +2%, -4%
Ground
Separate ground wire from air conditioners and building, and D-class grounding
with ground resistance of 100
Ω
or less.
Electricity
AC input more than 102W
Inrush Current
Maximum 100A
Ensure installation environment that avoids lowering voltage to power supply
equipment at the time of power-on due to the inrush current, although there's no
impact from the inrush current in normal use.