5/14/2018
Fuling Inverter User Manual - slidepdf.com
http://slidepdf.com/reader/full/fuling-inverter-user-manual
19/54
- 3 1 -
- 3 2 -
Function
Code
Name
Setting Range
Modifi
cation
Serial
No
F4.13
FDT level detection value
0.00 F0. 04
~
50.00Hz
110.
※
F4.16
Brake Threshold
Value Voltage
115.0 140.0%(standard DC bus
voltage) 380V
~
130.0%
113.
115.0 140.0%(standard DC bus
voltage) 220V
~
120.0%
F4.17
Speed display
ratio
0.1 999.9%
Speed=120 running
frequency F4.17/pole number
~
×
×
100.0%
114.
F4.18
PIDsetpoint
SourcesOp tion
0 Given by Keyboard(F4.19)
:
1 Given byAnalog Channel VI
:
2 Given byAnalog Channel CI
:
3 Given by Remote
Communication
:
4 Multi-segsetpoint
:
0
115.
F4.19
PIDFeedback
SourcesOp tion
0.0% 100.0%
~
0.0%
116.
F4.20
Preset PID setpoint
0 VI Feedback
:
1 CI Feedback
:
2 VI+CI Feedback
:
3 Communication feedback
:
0
117.
F4.21
PID Output Characteristics
Option
0 positive
:
1 Pnegative
:
0
118.
F4.22
Proportional gain (Kp)
0.00 100.00
~
1.00
119.
F4.23
Integral time (Ti)
0.01 10.00s
~
0.10s
120.
F4.24
Differential time (Td)
0.00 10.00s
~
0.00s
121.
F4.25
Sampling cycle time (T)
0.01 100.00s
~
0.10s
122.
F4.26
PIDcontrol
discrepancy limit
0.0 100.0%
~
0.0%
123.
F4.27
Feedback disconnection
detecting value
0.0 100.0%
~
0.0%
124.
※
※
※
※
※
※
※
※
※
※
※
※
F4.14
FDTdelay detectionvalue
0.0 100.0%(FDT level)
~
5.0%
111.
F4.15
Frequencyr eaching
detection range
0.0 100.0%(maximum frequency)
~
0.0%
112.
※
※
Function
Code
Name
Setting Range
Modifi
cation
Serial
No
F4.31
Multi-Speed 2
-100.0 100.0%
~
0.0%
128.
F4.32
Multi-Speed 3
-100.0 100.0%
~
0.0%
129.
※
※
F4.33
Multi-Speed 4
-100.0 100.0%
~
0.0%
130.
F4.34
Multi-Speed 5
-100.0 100.0%
~
0.0%
131.
F4.35
Multi-Speed 6
-100.0 100.0%
~
0.0%
132.
F4.36
Multi-Speed 7
-100.0 100.0%
~
0.0%
133.
F5.00
Motor Overload
ProtectionOption
0 No protection
:
1 normal motor
:
2 Variable Frequency motor
:
1
134.
F5.01
Motor Overload
ProtectionCurrent
20.0% 120.0%
(motor rated current)
~
100.0%
135.
F5.02
Power-down Frequency
Drop Point
70.0 110.0%(standard bus
voltage)
~
80.0%
136.
F5.03
Instantp ower-down
Frequency drop rate
0.00Hz F0.04
~
0.00Hz
137.
F5.04
Over-voltage
Stall Protection
0 prohibit
:
1 a ll ow
:
0
138.
F5.05
Over-voltage Stall
ProtectionVoltage
110 150%(380V)
~
120%
139.
110 150%(220V)
~
115%
F5.06
Auto limit current level
100 200%
~
200%
140.
F5.07
Limit current frequency
drop rate
0.00 50.00Hz/s
~
0.00Hz/s
141.
F6.00
Communication Address
1 247,0 is the broadcast address
~
1
142.
F6.01
Baud rate setting
0 1200BPS
:
1 2400BPS
:
2 4800BPS
:
3 9600BPS
:
4 19200BPS
:
5 38400BPS
:
3
143.
※
※
※
※
※
※
※
●
※
※
※
※
※
※
F5 Protection Parameters
F6 Communication Parameters
F4.28
Feedback disconnection
detecting time
0.0 3600.0s
~
1.0s
125.
F4.29
Multi-Speed 0
-100.0 100.0%
~
0.0%
126.
F4.30
Multi-Speed 1
-100.0 100.0%
~
0.0%
127.
※
※
※
2:Even check O,8,1 forRTU
(
)
F6.02
Data pattern
144.
0:No check N,8,1 for RTU
(
)
1:Oddcheck E,8,1 for RTU
(
)
※
0
Default
Value
Default
Value