Option: setting parameter=the sum total of display code for example:
require to display at operation status:Output current,Running speed,Output power 4+16+32=52, then
setting F3.05to 52 its corresponding parameter can be viewed at operation through pressing button
"DATA".
This I/O terminal status is displayed in decimal system, S1 (MO1) corresponding to the lowest digit.
For instance, input status displays 3 is indicting that terminal S1 and S2 are closed and others are open.
For details, please see F3.17 and F3.18 description.
,
,
These functions only can be viewed but can not be modified.
IGBT module temperature: indicates the temperature of the inverter IGBT module.
Over-temperature protection value of different inverter may be different.
Software version: software version number.
Inverter accumulative operating time: displays current inverter accumulative operation time.
Record three recent fault typ es: 0 is no fault; 1~22 is 22 different kinds of fault. For details,please see
fault analysis.
- 5 5 -
- 5 6 -
This function isto se t up the logical relationship between Local and external keyboard key-press.
Note: No. 3 function should be used cautiously. Maloperation may cause serious consequences.
4
8
16
32
64
12 8
256
Input terminal status
Output terminal status
PID setpoint
PID feedback
VI value
CI value
Current segment of
multi-speed control
1
2
Setting frequency
DC bus voltage
Code
Displayed Message
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
Code
Displayed Message
0:Setting frequency
1:Running frequency
2:Output current
3:Output voltage
4:Running speed
5:Output power
6:Output torque
7:DC bus voltage
8:PID setpoint
9:PID feedback
10:Input terminal status
11:Output terminal status
12:VI value
13:CI value
14:Current segment of
multi-speed control
operation status display
Stop status display
F3.04
Keypad display option
0
0 external keyboard preferential
ENB
:
1 Local and external keyboard
simultaneous display, only
external key-press is valid.
:
2 Local panel and external
keyboard simultaneous display,
only Local key-press is valid.
:
3 Local and external keyboard
simultaneous display, and all
key-presses are valid (both are
OR logicalrelation)
:
Function
Code
Name
Setting Range
Default
Value
F3.08
IGBT module temperature
0 1 00 .0
~
℃
F3.09
Software version
F3.10
Accumulative operating
time
0 65535h
~
0
Function
Code
Name
Setting Range
Default
Value
Function
Code
Name
Setting Range
Default
Value
F3.11
The fault before previous fault type
F3.12
Previous fault type
F3.13
Current fault type
255
0-1023
255
0-32767
F3.05
operation status display parameter option
F3.06
Stop status display parameter option
Function
Code
Name
Setting Range
Default
Value
0
0-14(0:invalid)
F3.07
operation status display p eferential option
r