background image

Ver.01

DIGITAL THERMOSTAT

WITH EVENT SCHEDULE

1. DESCRIPTION

Digital temperature controller and display conjugated to a time programmer with up to four daily events,
all with adjustable start and end. Its internal quartz synchronizer clock remains accurate for more than
60 years, even at frequent and often long power shortages.

•Air-conditioning
• Water heaters
• Counters with static coil

RT-607Ri power - 115 or 230Vac ± 10% (50/60Hz)
RT-607RiL power - 12 or 24 Vac/dc

-50 to 105°C

58 to 221°F

0.1°C between -10 e 100°C and 1°C in the rest of the range
1°F between -58 and 221°F

2. APPLICATION

3. TECHNICAL SPECIFICATIONS

- Power supply:

- Control temperature:

- Resolution:

-

- Dimensions:
- Operating temperature:
- Operating humidity:
- Sensors:
- Control outputs:

71 x 28 x 71mm

0 to 60°C / 32 to 140°F

10 to 90% RH (without condensation)

S1- Thermostat sensor (black)

THERM - Thermostat control output - 16(8)A/ 240Vac 1HP

Press

for 2 seconds until

, appears, and then release the key. The set working temperature

will appear. Use the

and

keys in order to change the value and, when ready, press

to

record.

Press

and

simultaneously for two seconds until it

, appears, then releasing it. When

appears, press

(short hit) and enter the code (123) through keys

and

. To confirm,

press the key

. Through keys

and

access the other functions and proceed in the same

manner to adjust them.
To leave and return to normal operations, press

(long hit) until

appears.

4. CONFIGURATIONS

4.1 - Control temperature setting (SETPOINT)

4.2 - To enter into the functions menu

SET

SET

SET

SET

SET

4.3 - Functions

Access code entry
Advanced configuration functions
Events planner operating mode
Scheduling in the events planner
Adjustment of the clock and the day of the week

Description

Min

Max

Unit

CELSIUS

Fun

Standard

Standard

Min

Max Unit

FAHRENHEIT

0.1

-5.0

-50.0

-50.0

0

0-no

0

20.0

5.0

105.0

105.0

999

1-yes

999

°C

°C

°C

°C

-

sec.

-

min.

°F

°F

°F

°F

-

Sec.

-

min.

36

9

221

221

999

1-yes

999

1

-9

-58

-58

0

0-no

0

2

0

-58

221

0

0-no

0

4.4 - Parameters table

4.4.1 - Parameters description

Temperature control differential (hysteresis)

Indication Offset

and

Minimum and Maximum limits of adjustable temperature

Operation mode for the thermostat

Minimum time of off thermostat output

It is the temperature difference (hysteresis) between turning the refrigeration or heating ON and OFF.
Example: When you wish to control the temperature at 4.0 ºC with a 1.0 ºC differential. In the case of
refrigeration, it shall be turned off at 4.0°C and turned on again at 5°C
In the case of heating, it shall be turned off at 4°C and turned on again at 3°C

Permits to compensate for any possible deviations in the reading of the room temperature (S1), resulting
from the sensor replacement or change in the cable length.

Limits whose purpose is to avoid that, by mistake, the temperatures are exaggeratedly set too high or too
low with relation to the setpoint.

This function allows setting the thermostat operation mode:

Refrigeration
Heating

Minimum time during which the thermostat output shall remain off before being reactivated. This field is
also used as activation delay when the controller is turned on.

Hitch thermostat to event schedule

Weekly programming

Programming for business days

Daily programming

This option allows linking the thermostat output operation (THERM) to the event schedule. If option 0
(no) is selected, the thermostat output shall be controlled by the temperature alone.
In the case of option 1, the thermostat option shall be controlled by the temperature and may only be
activated in a valid event in the event schedule.

In this option, you can choose how the events schedule will operate.

- In this mode, the instrument can configure up to four events for every day

of the week

- In this mode, the instrument keeps the events the same for

business days (Monday through Friday), and allows the programming of different events for
Saturday and Sunday.

- In this mode, the instrument keeps the events the same for all of the days of

the week.

4.4.2 - Events schedule operating mode

Manual activation time for events output

Time that output events is active when it is activated manually. Once this period of time is over, the output
events returns to function automatically.

4.4.3 - Programming of the events schedule

In this option, you can enter the values for the time periods for each event. The entry of the data depends
on the operating mode configured. You can configure up to four events for each day. For each event you
configure the start time and the end time through options

until

where:

Start time for the first event
End time for the first event

Start time for the fourth event
End time for the fourth event

If you do not need to use the four events, you can configure it to be deactivated, and all you have to do is
increase the off time (

for example) until the

indication appears. It is also possible to configure

an event to overlap at midnight, and for that you should increase the off time until the option

appears

and adjust an event for the next day to start at 00h and 00min. According to the operating mode
configured, the following scheduling possibilities may be presented.

4.4.4 - Adjustment of the current time and day of the week

5. FUNCTIONS WHIT FACILITATED ACCESS

5.1 - Visualize the current time

After entering the function menu, press key

repeatedly until the message

appears Hit

key

. The settings will appear in the following order:

Ex.: 12h43min - Friday

Hours
Minutes
Day Of The Week

Quickly pressing the key

, you can visualize the time set in the controller, the current time will be

shown, followed by the minutes and then the day of the week.

Ex.: 12h43min - Friday

Hours
Minutes
Day Of The Week

HOURS

MINUTES

DAY OF THE WEEK

SET

SET

RT-607Ri

power

Temperature control differential (hysteresis)

Indication Offset

Minimum limit of adjustable temperature

Maximum limit of adjustable temperature

Operation mode for the thermostat

Minimum time of off thermostat output

Hitch thermostat to event schedule

Manual activation time for events output

1.0

0

-50.0

105.0

0

0-não

0

R

T607PWV01-01T-12360

THERM

EVENT

Reviews: