DIGITAL CONTROLLER FOR 

REFRIGERATION AND DEFROST

 WITH ALARM OUTPUT

Ver.04

TC-940Ri

TC940V04-03T

-10789

UL-Underwriters Laboratories

1. DESCRIPTION

TC-940Ri

 is a digital controller of temperature that manages defrost cycles and evaporator fans. 

This instrument also has an output for alarm.
An innovative feature of TC-940Ri is the possibility that the controller offers initiating a defrost cycle 
evaporator temperature, detecting the moment that the system needs to do defrost. Thus, it is possible 
to save energy and increase the efficiency of the system.

2. APPLICATION

• Refrigeration counters
• Refrigerated balcony

3. 

/ -58 to 167°F

 /  1°F

Product in agreement with CE (European Community) and UL Inc. (USA and Canada).

TECHNICAL SPECIFICATIONS

- Power supply:

TC-9

40

Ri - 115/230 Vac ±10% (50/60 Hz) 

                           TC-940RiL - 12/24 Vac/dc

- Control temperature:

 -50 to 75° C

 

- Resolution: 

0.1°C from -10 to 75°C and 1°C outside this range

 

- Operating temperature: 

0 to 50°C

 / 

32 to 122°F

- Operating humidity: 

10 to 90% RH (without condensation)

- Dimensions:

 71 x 28 x 71mm

- Load current (outputs): 

REFR: 5(3)A / 250Vac 1/8HP (compressor, solenoid valve or contactor)
FANS: 5(3)A / 250Vac 1/8HP (evaporator fans) 
DEFR: 5(3)A / 250Vac (defrost - resistance or hot gas)
ALRM: 3A / 250Vac resistive load (external alarm)

 / 167°F and 257°F

 

CLASSIFICATION ACCORDING TO IEC60730-2-9 STANDARD:

 

- Temperature limit of the installation surface:

 50°C

 / 

122°F  

- Type of construction:

 Built-in electronic controller  

- Automatic action:

 Type 1

- Control of pollution:

 Level 2 

- Impulse voltage:

 1,5kV   

- Temperature for the test of sphere pressure:

 75°C and 125°C

 

- Insulation:

 Class II

4. CONFIGURATIONS

4.1 - Control temperature adjust (SETPOINT)

Press          for  2  seconds  until  appears            ,  and  release  it  after  that.  The  adjusted  operation 
temperature will appear. Use the keys        and        to change the value and then press         to record it.

SET

SET

Access code: 123 (one hundred and twenty-three)

Control differential (hysteresis)

Offset indication for ambient sensor

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Defrost type (0 = resistance; 1 = hot gas)

Initial defrost condition (0 = time; 1 = temperature)

Period between defrost (if F07 = 0)

Maximum time in refrigeration (for security, if F07 = 1)

Temperature in the evaporator for defrost start (if F07 = 1)

Time of pre-defrost (if F07 = 1)

Defrost when the instrument is powered on (0 - no; 1 - yes)

Evaporator temperature (S2) to finish defrost cycle

Maximum defrost duration (for security)

Fan turned on during defrost (0 - no; 1 - yes)

Delay to do the first defrost (if F07 = 0)

4.2 - Parameters table

Description

Min Max Unit

CELSIUS

Fun

Standard Min Max Unit

FAHRENHEIT

F01

F02

F03

F04

F05

F06

F07

F08

F09

F10

F11

F12

F13

F14

F15

F16

-99

0.1

-20

-50

-50

0

0

1

1

-50

-50

0

999

20.0

20.0

75.0

75.0

1

1

999

240

75.0

90

75.0

90

999

-

°C

°C

°C

°C

-

-

min.

hour

°C

min.

-

°C

min.

-

min.

-

1.5

0.0

-50

75.0

0

0

240

24

-5.0

10

40.0

45

-99

1

-36

-58

-58

0

0

1

1

-58

0

0

-58

0

0

999

36

36

167

167

1

1

999

240

167

90

167

90

999

-

°F

°F

°F

°F

-

-

min.

hour

°F

min.

-

°F

min.

-

-

-

3

0

-58

167

0

0

240

24

23

10

104

45

Standard

F17

F18

F19

F20

F21

F22

F23

F24

F25

F26

F27

F28

F29

F30

F31

F32

F33

0

-50

0

-50

0.1

-50

0.1

-50

0.1

0

0

0

0

0

0

30

75.0

3

75.0

20.0

75.0

20.0

75.0

20.0

999

999

999

999

999

1

-

min.

°C

min.

-

°C

°C

°C

ºC

°C

°C

min.

min.

min.

sec.

sec.

-

10

0.0

1

1

75.0

2.0

-50

1.0

75.0

1.0

0

0

0

0

0

1

0

-58

0

-58

1

-58

1

-58

1

0

0

0

0

0

0

30

167

30

1

167

36

167

36

167

36

999

999

999

999

999

1

-

min.

°F

min.

-

°F

°F

°F

ºF

°F

°F

min.

min.

min.

sec.

sec.

-

10

32

1

1

167

4

-58

2

167

2

0

0

0

0

0

1

Temperature indication (S1) locked during defrost
(0 - no; 1 - yes)

Draining time (dripping of defrost water)

Evaporator temperature (S2) for fan return after 
draining

Maximum time for fan return after draining 
(fan-delay)

Fan on with compressor off 
(refrigeration) 

(0 - no; 1 - yes)Fan stop for high temperature in evaporator

Differential for fan return (after stoping for high temperature 
in evaporator)

Low temperature alarm (S1)

Alarm differential of low temperature

High temperature alarm (S1)

Alarm differential of high temperature

Inhibition time of alarm when the instrument is powered on

Inhibition time of alarm after draining

Delay when the instrumet is powered on 

Minimum time of compressor turned on

Minimum time of compressor turned off

Compressor status with detached ambient sensor 
(0 = off; 1 = on)

4.3 - Parameters description

F01 - Access code (123)

It is necessary to change the configuration parameters. To visualize the adjusted parameters, it is not 
necessary to insert this access code.

F02 - Control differential (hysteresis)

It is the difference of temperature (hysteresis) between ON and OFF the refrigeration.

Example:

 You need to control temperature in 4.0 ºC with differential of 1.0 ºC.

So, the refrigeration is turned off in 4.0 ºC and will be turned on in 5.0 ºC (4.0 +1.0).

F03 - Offset indication for ambient sensor

It allows to compensate eventual shuting lines on reading of ambient temperature (S1), proceeding of 
sensor exchange or cable length alteration.

F04 - Minimum setpoint allowed to the end user

F05 - Maximum setpoint allowed to the  end user

It is to prevent that incorrect high or low temperatures be regulated.

F06 - Defrost type

“0” = Electrical defrost (resistances),where is kept on only the defrost output.
“1” = Hot gas defrost, where defrost and compressor outputs are kept on.

F07- Initial defrost condition

It defines if the defrost start will be for temperature or time. Is this function has the value “1”, when the 
evaporator temperature reaches the configured value in “F10” the instrument starts to count the pre-
defrost time and, after, will do the defrost.

F08 - Period between defrosts (if F07 = 0)

It determines the time between two consecutives defrost cycles, and starts to be counted from the last 
defrost. Attention, the defrost only will start if the temperture in S2 (evaporator sensor) is lower than F13.

F09 - Maximum time in refrigeration (for security, if F07 = 1)

It acts as security time if (F07 = 1) and evaporator temperature will not reach the configured value in 
“F10”. This function determines the maximum time that controller will stay without defrost.

F10 - Temperature in the evaporator for defrost start (if F07 = 1)

When evaporator temperature reaches the configured value in this function the controller will start to 
count the pre-defrost period (F11).

F11 - Time of pre-defrost (se F07=1)

At the moment that the temperature in evaporator decreases and reaches the configured value in “F10”, 
start to be counted the pre-defrost time. During the pre-defrost stage, if the temperature is kept low the 
defrost starts, else if the temperature increase at least 1 ºC in relation to configured value, the system 
returns to refrigeration stage.

 

F12 - Defrost when the instrument is powered on

It possibilities the defrost at the moment that the  controller is turned on, for example, in return of electrical 
energy (in case of energy lacks).

F13 - Evaporator temperature (S2) to finish defrost cycle

If  evaporator temperature (sensor S2)  reaches the  adjusted value, the  end  defrost will  happen for 
temperature. With this , the defrost process is optimized.

F14 - Maximum defrost duration 

This function serves to adjust the maximum value of time to defrost. If in this period the evaporator 
temperature will not reach the configured value in F13 a point will be blinking on inferior down right side of 
display indicating that the end defrost ocurred for time and not for temperature.
This can happen when the adjusted temperature is very high, the limit time will be not enough, the S2 
sensor is detached or not in contact with the evaporator.

F15 - Fan turned on during defrost

It possibilities the fan functioning during defrost.

F16 - Delay to do first defrost (if F07=0

)

This function defines an extra time that the instrument will keep in refrigeration before do the first defrost, 
to prevent that lot of counters enter in defrost at the same time. This time only appears before the first 
defrost, when F07 = 0 (initial defrost for time).

F17 - Temperature indication (S1) locked during defrost

This  function  prevents  that  ambient  temperature  elevation  be  visualized.  During  defrost  the  last 
measured temperature in refrigeration cycle will be locked on display. The indication will be released 
when this temperature will be reached again or 15 mintes after the ibegin of next refrigeration cycle.  

F18 - Draining time (dripping of defrost water)

Necessary time for dripping, it means, to drain the last water drops of the evaporator. All the outputs 
keep turned off. If you do not need this stage, adjust this time for ”zero”.

F19 - Evaporator temperature (S2) for fan return after draining(fan-delay) 

After the draining, the fan-delay cycle starts. The refrigeration (REFR.) output is turned on, because the 
evaporator temperature is high, but the fan only is turned on after evaporator temperature decreases the 
adjusted value. This process is necessary to remove the heat that exists in the evaporator because the 
defrost, preventing to pass it pass it to the ambient.