JGASUK-IOMM-2015-2
Fulton Ltd
Page 38
MAINTENANCE - 4
4.12.1
TROUBLESHOOTING BOILER
Problem
Cause
Remedy
Ignition Failure
1. Power Supply
Check fuse or circuit breaker.
Reset or Replace as required.
2. Ignition Electrodes
Check for cracks in porcelain,if found replace the
electrode. Check electrodes for carbon build-up.
Clean as required.
Check settings, adjust if required.
3. Transformer
Check voltage between transformer leads at terminal
block to be sure transformer is live.
4. Burner Control
Check voltage between ignition terminal and neutral,
this check must be made before the control locks
out. If no power, replace the control.
5. Air Settings
Check main air adjustment and secondary air
adjustment.
6. Faulty Air Switch
Check for faulty air switch.
7. Gas Valve
Check filters in the valve block. Clean as
required.
8. Gas supply
Check for gas pressure and intermittent supply
problems.
9. Loose wire connections
Check connections to all components.
Flame Failure During
Start-up
1. Power Supply
Check fuse or circuit breaker.
Reset or replace as required.
2. Gas supply
Check for gas pressure and intermittent supply
problems.
3. Air Settings
Check main air adjustment and secondary air
adjustment.
4. Ignition Electrodes
Check electrodes for carbon build-up.
Clean as required. Check for proper adjustment,
readjust if necessary. Check for cracks in porcelain,
if found replace the electrode.
5. UV Detector
Check the detector is located correctly and clean.
6. Burner Control
Check voltage between ignition terminal and neutral,
this check must be made before the control locks
out.
If no power, replace the control.
7. Loose wire at fuel valve
circuit.
Tighten wiring connections.
8. Contact open on Air Switch
Adjust to the correct setting.
9. UV Detector wiring reversed
at control box.
Change to the correct terminals.
Flame Failure During
Normal Run
1. Power Supply
Check fuse or circuit, reset or replace as necessary.
2. Gas Supply
Check gas pressure coming into the gas train, if low
contact the gas supplier.
Check the setting on the gas valve regulator, adjust
as required.
3. UV Detector
Check the detector is located correctly and clean.
4. Faulty Air Switch
Check for faulty air switch.
5. Bad Combustion
Check combustion readings.
CONTINUED ON NEXT PAGE
Summary of Contents for J Series
Page 2: ...JGASUK IOMM 2015 2 Fulton Ltd Page II ...
Page 54: ...JGASUK IOMM 2015 2 Fulton Ltd Page 48 APPENDIX A ...
Page 58: ...JGASUK IOMM 2015 2 Fulton Ltd Page 52 APPENDIX A ...
Page 60: ...JGASUK IOMM 2015 2 Fulton Ltd Page 54 ...
Page 62: ...JGASUK IOMM 2015 2 Fulton Ltd Page 56 ...