TROUBLESHOOTING GUIDE

Symptom

Possible cause

Recommended action

8. Fan has stopped.

Power supply problem

Check power supply.

Connector short circuit

Check for moisture in the motor connection.

Stuck impeller

Check for any foreign objects in the fan housing.

Check that no ice has formed in the fan housing.

Make sure motor bearings are functioning.

9. Fan performance 

loss.

Motor winding

Check the resistance between windings.

Debris

Check for any foreign objects in the fan housing.

Incorrect rotational direction

Check rotational direction.

Connections

Check that connections and duct routing are correct.

7 Troubleshooting

Troubleshooting with the power switched 
on may only be carried out by a licenced 
electrician.

7.1 Troubleshooting guide

The troubleshooting guide contains information for 
identifying faults which are simple to rectify. Always 
perform the troubleshooting procedures before  
contacting FUMEX.

8 Maintenance

Please remember that only original spare 
parts may be used.

Make sure that all moving parts are secured to prevent 
unintentional movement.

8.1 Cleaning

The product should be cleaned with clean cloths and 
neutral detergents to avoid damage.

MAINTENANCE SCHEDULE

Interval

Item

Inspection module

Maintenance instructions

Date

When  

necessary

1.1

Fan

Clean exterior. See section 

8.1 Cleaning

.

Every six 

months

2.1

Electrical equipment

Check all electrical equipment for visible external  

damage. Replace if necessary.

2.2

Fan housing

Check for leaks, damage and wear.

2.3

Motor

Check functionality. Replace if necessary.

2.4

Impeller

Check for any damage and clear away foreign objects if neces-

sary. Replace a damaged impeller.

2.5

Fan housing

Check that connections are secure and clear away foreign 

objects. Check the drainage hole and clear if necessary.

8.2 Maintenance schedule

Depending on the changing operating con-
ditions between the different systems, the 
intervals for recommended maintenance 
may differ. Users should therefore determine 
their own maintenance intervals.

The checklist for maintenance is designed for normal 
use of the machine. The recommended intervals are 
approximate and refer to the time after the first start-up.
FUMEX recommends the following maintenance  
schedule:

Summary of Contents for FBE 1100 LG 0

Page 1: ...FBE 1100 Manual ...

Page 2: ...manual 3 1 2 Declaration 3 1 3 Warranty 3 1 4 Manufacturer 3 2 Safety 4 2 1 General 4 2 2 Protective equipment 4 2 3 General warnings information 4 3 Product Description 5 3 1 Serial number product name 5 3 2 Labels and safety signs 5 3 3 Areas of Use 6 3 4 Design 6 3 5 Function 6 4 Preparation for use 7 4 1 Transport storage 7 4 2 Electrical equipment 7 4 3 Assembly installation 7 4 3 1 Unpacking...

Page 3: ... being voided The warranty period is one year from the date of pur chase and covers the product and its constituent parts All manufacturing defects are covered by the warranty FUMEX replaces defective parts in accordance with NL 17 FUMEX is not liable for any consequential or incidental damage or any loss of income as a result of or in con nection with the warranty case The onus is on the buyer to...

Page 4: ...icky dust must not be sucked into the fan If this occurs pre filtration must be used or regular cleaning carried out All work on the machine must be carried out by certified and authorised personnel For maintenance work where contact with dust occurs personal protective equipment such as safety glasses respiratory protec tion and safety gloves must be worn The surface on which the machine is insta...

Page 5: ... Frequency ErP n ErP cat ErP N www fumex com 1 2 3 1 2 3 Manual FUMEX FBE 1100 3 Product Description 3 1 Serial number product name Refer to the product nameplate 3 2 Labels and safety signs Safety signs that are missing or illegible must be replaced before the machine is used According to Fig 1 1 Fumex logotype 2 Nameplate 3 Motor rotation arrow Fig 1 ...

Page 6: ... Design See Fig 2 1 Fan housing 2 Outlet 3 Outlet grille 4 Lifting eye 5 Motor plate 6 Motor 7 Cooling air intake 3 5 Function Air is sucked through the inlet cone 13 Fig 2 to the center of the fan wheel 12 The air is then sucked through the fan wheel and evacuated through the fan outlet 2 Fig 2 8 Cooling fan 9 Lifting eye motor 10 Junction box 11 Inlet 12 Impeller 13 Inlet cone ...

Page 7: ...ng from frequency converters If control devices e g frequency converters are used the manufacturer s recommenda tions to avoid interference are followed For example EMC protective earth cable length cable shielding etc The choice of cable and cable area must comply with the national requirements applicable to fixed installa tions For electrical installation see Section 10 2 Circuit diagram electro...

Page 8: ...o that fan wheels are not damaged The motor package must always be installed so that the cable connection is facing down wards after installation When installing motor packages apply liquid gasket for sealing between the motor plate and fan housing Fumex recommends the HYLOMAR brand Procedure Upon modification of configuration refer to Fig 4 and Fig 5 Fig 4 Fig 5 Fig 6 Fig 8 Fig 9 4 3 4 Possible c...

Page 9: ...r and does not require drainage as the outlet is the lowest point Suitable in the event of condensation problems On roofs At locations with heavy precipitation founda tions must be built on site See Fig 10 Fig 10 Fig 11 Fig 12 On facades Wall mounting on bracket according to Fig 11 optimises pressure drops on the inlet side 4 3 6 Installation The fan is designed for installation in an industrial p...

Page 10: ...x4 2 x2 620 70 50 650 Manual FUMEX FBE 1100 4 4 Accessory installation Accessories ordered separately Refer to Chapter 11 Accessories Spare Parts 4 4 1 Flexible duct FBD 750 Fig 13 Fig 14 4 4 2 Transition FBO 1100 4 4 3 Mounting rail FBM 1100 Fig 15 ...

Page 11: ...pping the fan As the speed decreases you can see which way the motor is rotating through the cooling air intake pos 7 Fig 2 If the direction of rotation is incorrect the phase coupling in the motor terminal block is reversed 3 Check the rotational direction again 4 Turn off the fan The fan is now ready for operation 6 Operation The fan motor generates heat and is equip ped with a cooling fan pos 8...

Page 12: ...ure that all moving parts are secured to prevent unintentional movement 8 1 Cleaning The product should be cleaned with clean cloths and neutral detergents to avoid damage MAINTENANCE SCHEDULE Interval Item Inspection module Maintenance instructions Date When necessary 1 1 Fan Clean exterior See section 8 1 Cleaning Every six months 2 1 Electrical equipment Check all electrical equipment for visib...

Page 13: ...ning and disassembly of the product may only be done by authorised personnel wearing protective gear The handling and correct removal of the various types of materials must be in accordance with the applicable legal requirements Please contact FUMEX if you have any questions about the various types of waste ...

Page 14: ...ncy 50 Hz Power 11 kW Current 19 6 A Speed 2950 rpm Enclosure class IP55 Sound level Lp 94 dB A Temperature limits Max operating temperature 80 C Ambient temperature 20 C till 40 C Transport storage temperature 25 C till 60 C Max humidity 80 Sound pressure level 1 meter from fan at hemispherical sound propagation in free field 10 Technical information ...

Page 15: ...L1 L2 L3 PE 400V 3 D U1 Z2 V1 U2 Z1 V2 L1 L2 L3 PE 690V 3 Y U1 Z2 V1 U2 Z1 V2 MA1 5 4 3 2 1 8 7 6 9 11 10 13 14 12 17 16 15 18 Manual FUMEX FBE 1100 10 2 Circuit diagram electronics 10 3 Exploded view drawing ...

Page 16: ...lar to round coupling Fig 17 Safety switch SSB 1100 With lockable toggle Two M25 penetrations included Fig 22 Fig 23 Fig 24 Safety switch SSB 1100 EMC For operation via frequency converter Copper sheathed with lockable toggle Two M25 bushings included Contactor SKO 3 pin contactor with overcurrent relay for manual reset The overcurrent relay has phase loss protection Used in together with external...

Page 17: ...17 Manual FUMEX FBE 1100 12 Notes ...

Page 18: ...18 Manual FUMEX FBE 1100 ...

Page 19: ...19 Manual FUMEX FBE 1100 ...

Page 20: ...X SUPPLIES EXTRACTION ARMS VEHICLE EXHAUST EXTRACTION FANS FILTERS CONTROLS WORKSHOP EQUIPMENT Verkstadsvägen 2 93161 Skellefteå Sweden Tel 46 910 361 80 Fax 46 910 130 22 E mail info fumex se www fumex com ...

Reviews: