function Innovation & Technology AS
- 10 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
7.
PIR sensitivity
can be adjusted from 20 to 100, where 20 is the highest
sensitivity. This parameter is default set to 40 and should not be set lower than
this value without testing for false detection.
5.1.1
Master function ”Movement General”
The “Movement General” can be re-trigged from another sensor like switches and
movement detectors. It is necessary to set the “Write” flag in the object 3 “Movement
General” to make the object re-triggable. Se Figure 5
.
Figure 5 - Object flags for re-triggable "Movement General" object
5.1.2
Slave function ”Movement General”
The “Movement General” could be configured with “Slave” functionality. The slave
functionality can be enabled by setting the recovery time and the cyclic sending time to a
lower value than the Master (master detector recovery time or staircase timer). The
reaction at the end of detection must be set to “No reaction”.
5.1.3
Cyclic sending
If the value of cyclic sending is lower than the recovery time, the sensor will not send any
cyclic ON telegrams. If the two values are the same, the sensor sends one cyclic sending
right before the recovery time elapses. The cyclic sending time will not be affected by a
re-trigged recovery time.
It is not possible to re-trigg the
“Movement Local”
by object. This object can only
be re-trigged by the local movement detector.