5.4
Object list
Table 2 - Object list for the Movement Sensor
ID
Name
Description
Configuration
OBJ 003
Movement:
General
When the movement detector
detects movement Obj. 003 either
sends a “1” or “No reaction”
depending on parameter “Reaction
at start of detection”.
At the end of detection (when the
“Recovery time” has elapsed) the
object will be transmitted either
with a “0” or “No reaction”.
The object can be set to cyclic
sending depending on parameter
“Cyclic sending”.
1 bit
1.001
C - (W) T
OBJ 004
Movement:
Local
This object can be configured by
parameter “Separate Movement
Local” to either “Disabled”, “Semi
automatic” or “Full automatic”. In
Semi automatic mode it will only
transmit at the end of detection.
In “Full automatic” the object will
transmit both at the start of
detection and at the end of
detection.
This object is not cyclic.
The object can also be dependent
on the “Lux Threshold Switch”
1 bit
1.001
C - - T
Table 3 - Object list for the LUX Sensor
ID
Name
Description
Configuration
OBJ 005
Lux Sensor:
Current value
(lux)
Writing a LUX value to this obj. will
calibrate the value from the sensor.
The calibration will NOT be
overwritten when new ETS software
is downloaded. The calibration and
the lux value written to Obj. 005 will
be stored permanently in
EEPROM/flash.
2 byte
9.004
C R W -
OBJ 006
Lux Sensor:
Lux threshold
switch
The object transmits a 1, 0 or no
action depending on the Current
value (lux) and the threshold
parameters and the chosen action
from parameter.
The object can be sent cyclic.
It is possible to activate turn-on
and/or turn-off delay via
parameters.
1 bit
1.001
C - - T