function Innovation & Technology AS
- 15 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
6.3
Parameters
6.3.1
Comfort mode
The thermostat is using the “Base setpoint in ºC” as the regulator set-point for the
heating regulator in comfort mode. The heating regulator starts to heat if the actual
temperature falls below the base setpoint minus the parameter value for “Low hysteresis
in 0.1K".
The heating regulator will turn off the heat when the actual temperature rises above the
base setpoint. The regulator will turn off the heat at 21.0 ºC with the parameter settings
shown in Figure 9
The cooling system will turn on at the temperature "Base setpoint in ºC" + "Deadzone
between heating and cooling in 0.1K" + "High hysteresis in 0.1K". The cooling system will
be turned off when the temperature falls below the base set-point + deadzone. The
cooling system will be turned off at 21.0 + 2.0 = 23ºC with the parameter settings
shown Figure 9.
Figure 9 - Thermostat settings
It is the value from the object "Actual setpoint" that the regulator uses as the
temperature set-point. The “Actual setpoint” will change depending on the “Base
setpoint”, the active mode, if the regulator is in heating- or cooling mode and the
local temperature adjustment.