function Innovation & Technology AS
- 17 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
6.3.5
Basic heating and cooling stage
See the description of the different regulator modes in chapters 6.3.1 to 6.3.4.
6.3.6
Additional heating and cooling stage
The KNX MultiLight can control an additional heating and/or cooling system with ON/OFF
control. The temperature limits for the additional heating- and cooling systems can be
defined by parameters, see Figure 10 and Figure 11.
The additional heating stage will be turned on if the room temperature has dropped 2ºC
below the parameter settings in the thermostat parameter window, see Figure 9. The
hysteresis for the additional heating stage is fixed to +0.5ºC.
The additional heating stage will turn on if the temperature falls below 21ºC - 2.0ºC =
19ºC and turn off at 21ºC - 2.0ºC + 0.5ºC = 19.5ºC in comfort mode according to the
parameter settings shown in Figure 9 and Figure 10.
Figure 10 - Heating parameter windows
Figure 11 - Cooling parameter windows
The additional cooling stage will be turned on bases on the stage offset from basic to
additional stage, see Figure 11. The additional stage cooling will turn on if the
temperature rises above 23ºC + 2.0ºC = 25ºC for comfort mode (see parameters Figure
9). The additional stage will turn off at 23ºC + 2.0ºC - 0.5ºC = 24.5ºC