function Innovation & Technology AS
- 22 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
The object can be set either to read
only or read/write by parameter.
The updated value can either be
stored in EEPROM or in volatile
memory.
This object can be set to cyclic
sending.
OBJ 010
Thermostat:
Actual setpoint
The actual setpoint value that the
regulator is using. This can be
either the Comfort-, standby-,frost-
temperature with the local
adjustment (obj. 011). The object
will transmit on change, so the
setpoint will be transmitted when
the regulator change mode.
This object can be set to cyclic
sending by parameter.
2 byte
9.010
C R - T
OBJ 011
Thermostat:
Local adjustment
of temp offset
The object holds the local
adjustment of temperature offset.
This object can be updated either
from KNX or from the user panel.
Maximum adjustment is +/- 3K from
the user panel and +/-10K from the
object.
2 byte
9.002
Flag: C - W T
OBJ 012
Thermostat:
Comfort mode
The regulator goes to Comfort-
Mode regulator setting if this bit is
set.
This mode has 2. priority
1 bit
1.001
C - W -
OBJ 013
Thermostat:
Night mode
The regulator goes to Night-Mode
regulator setting if this bit is set.
This mode has 3rd priority
1 bit
1.001
C - W -
OBJ 014
Thermostat:
Frost/Heat
protection mode
The regulator goes to frost/heat
protection mode regulator setting if
this bit is set.
Frost mode setpoint
is permanent at 10ºC. Heat
protection setpoint is 35ºC (fixed
limits).
This mode has 1. priority
1 bit
1.001
C - W -
OBJ 015
Thermostat:
Control value
basic heating
Switch
The output of the basic heating
regulator. This object is set high if
the actual temperature (obj. 007) is
lower than obj. 010 “Actual
setpoint” - hysteresis. The heating
will be turned off when the actual
temperature (obj. 007) goes above
“Actual setpoint” (obj. 010).
Cyclic sending every 40 min.
1 bit
1.001
C R - T
OBJ 016
Thermostat:
Control value
basic heating
Continuous
The output of the PI regulator with
the proportional factor and reset
time from the parameter settings.
The object can be automatically
transmitted based on a %-value
change (set by parameter).
The integral part can be disabled by
setting the reset time parameter to
0, resulting in a P-regulator.
Cyclic sending every 40 min.
1 byte
5.001
C R - T