function Innovation & Technology AS
- 23 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
OBJ 017
Thermostat:
Control value
basic heating
Feedback
This object gives the status of the
basic heating stage. If the control
value for basic heating is 1% or
more this object will be set to “1”
and the red heating indication in the
user panel will be lit.
1 bit
1.001
C R - T
OBJ 018
Thermostat:
Control value
additional heating
Switch
The additional heating stage is set
high if the temperature falls below
the basic setpoint - parameter
settings for the different modes and
local adjustment.
Permanent hysteresis: +0,5K.
Cyclic sending every 40 min.
1 bit
1.001
C R - T
OBJ 019
Thermostat:
Control value
basic cooling
Switch
The output of the basic cooling
regulator. The target cooling
temperature in comfort mode will
be ”Base set point” + ”Dead zone”
+ regulator mode temperature
parameter.
This object is set high if the actual
temperature (obj. 007) is higher
than the target cooling temperature
+ hysteresis. The cooling will be
turned off when the actual
temperature (obj. 007) falls below
the target cooling temperature.
Cyclic sending every 40 min.
1 bit
1.001
C R - T
OBJ 020
Thermostat:
Control value
basic cooling
Continuous
The output of the PI regulator with
the proportional factor and reset
time from parameter settings. The
object can automatically be
transmitted based on a %-value
change (set by parameter).
The integral part can be disabled by
setting the reset time parameter to
0, resulting in a P-regulator.
Cyclic sending every 40 min.
1 byte
5.001
C R - T
OBJ 021
Thermostat:
Control value
basic cooling
Feedback
Gives the status of the basic cooling
stage. If the control value for basic
cooling is 1% or more this object
will be set to “1” and the blue
cooling indication in the user panel
will be lit.
1 bit
1.001
C R - T
OBJ 022
Thermostat:
Control value
additional cooling
Switch
The additional cooling stage that is
set high if the temperature goes
above the basic se
de parameter settings for
the different modes. Permanent
hysteresis: +0,5K.
Cyclic sending every 40 min.
1 bit
1.001