function Innovation & Technology AS
- 34 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
11
Technical data
Data subject to change without notice
Power
-
Operating voltage, KNX
-
Power consumption, KNX
21...30 V DC,
Normally10mA, Peak17mA
Output relay
-
Number potential free contacts
-
Un rated voltage
-
In rated current
-
Power loss at max. load
1
250 V AC (50/60 Hz)
6A
1W
Output relay switching
power
-
Maximum inrush current
-
AC3 operation (cosφ
-4-1
-
AC1 operation (cosφ
-4-1
-
DC current switching capacity (ohmic load)
-
Mechanical endurance
60A/150uS
2A
6A
2A/30V DC
100.000
Inputs
-
Number of inputs
-
Polling voltage Un
-
Sensing current In
-
Permitted cable lengths
2
3,6V
0,5mA
2m
Connections
-
KNX
-
Load current circuits and inputs
-
Connection of sensor
via connection terminal, without screws
Wiring: 0,5-1,0 mm2
4-pol plug
Movementdetector
-
Sensor
Detection area 4 m if mounted in a
hight of 2 meters
EIB / KNX operating and
display elements
-
Thru separate control panel with plug and LEDs
Housing
-
IP20
EIB / KNX voltage
-
SELV 24 V DC (safety extra low voltage)
Temperature range
-
Operation
-
Storage
-
Transport
– 5 °C ... + 55 °C
– 25 °C ... + 65°C
– 25 °C ... + 65 °C
Design
-
Dimensions KNX Node (H x W x D)
-
Dimension Movement detector
-
Dimensions User panel
17,5 x 30,0 x 120,0 mm
21mm x Ø=31mm
154mm x Ø 14 mm
Weight
-
KNX node and movement detector
-
User panel
30g
29g
Approvals
CE mark
-
EIB / KNX nach EN 50 090-2-2
-
In accordance with the EMC guideline and low
voltage guideline.
Certification