General functions and user panel
The status of the KNX MultiLight is shown by the object “Self-Test status”. For normal
operational nodes this status object is low. If the movement sensor or user panel does
not respond the self test status is set high. The object can be configured to be sent cyclic
[1 to 24 hours].
The KNX MultiLight can be configured without a user
panel, with a standard or extended user panel. The
standard and extended user panel option includes a
temperature sensor, buttons for local adjustment of the
temperature set-point and LED indication of the local
adjustment.
The user panel will also show the status of the
temperature regulator by showing either a red light if
the temperature regulator is heating or a blue light if
the temperature regulator is cooling. The extended user
panel will also include up and down buttons and LED
indication for manual shutter control.
The temperature regulator is not available if the KNX
MultiLight is configured without a user panel.
The temperature sensor can be calibrated from the user panel. The calibration mode is
activated if both the + and – buttons are pressed for 5 seconds or more. In this mode
the temperature LED will start to blink for the calibration setting. The + and – buttons
will increase or decrease the measured temperature in steps of 0.5°C. So, the measured
temperature will be adjusted 1.5°C lower if the -3 LED is blinking. The adjustment has to
be acknowledged by pressing both the + and – button.
Table 1 - Object list for general and user panel objects
ID
Name
Description
Configuration
OBJ 000
Device:
Self-Test status
This object will report self test result
and alive status with a "0" if
everything is ok. If it sends "1" the
self test has failed.
The object can be set to cyclic
sending by parameter.
This object will be set if the
communication with the movement
detector or user panel has failed.
1 bit
1.001
C R - T
OBJ 001
Panel:
Shutter operation
– Stop/Step
This object will be visible if
parameter “Activation of user panel”
is set to “Extended user panel”.
The object will be transmitted with
a 1 or a 0 if the up or down button
is pressed (short operation)
1 bit
1.007
C - - T
OBJ 002
Panel:
Shutter operation
– Up/Down
This object will be visible if
parameter “Activation of user panel”
is set to “Extended user panel”.
The object will be transmitted with
a 1 or a 0 if either the up or down
button is pressed (long operation).
1 bit
1.008
C - - T