function Innovation & Technology AS
- 9 -
Manual – KNX MultiLight Art.nr 44001
Doc.no. D-TS-ML-K-005-A
5
Movement and LUX level detection
5.1
Movement sensor
The combined movement and LUX level sensor is connected to the MultiLight KNX node
through a 4-wire cable.
The communication object for the movement sensor, object 003 "Movement General",
has the following parameter settings:
Figure 4 - Movement sensor parameter window
1.
Recovery time
for detection from 1 to 255 minutes. The recovery time specifies
the time between the last detected movement and when the object is set low.
2.
Action for start of detection
can be ”ON” or “no reaction”.
3.
Cyclic sending On commands
of "Movement General" can be enabled or
disabled. The cycle time can be between 1 and 255 minutes. 0 disable the
function.
4.
Action for end of detection
can be ”OFF” or “no reaction”.
5.
Separate Movement Local object
The movement detector can be configured with an additional communication
object named “Movement Local”. This object can have the following functionality:
a.
Semi-automatic
: "Movement Local" object is not transmitted at start of
detection, but will transmitt a ”0” for end of detection. The object can be used
as a turn off function.
b.
Full automatic
: "Movement Local" object is transmitted both at start of
detection and end of detection. The object can be used to both turn on and off
a function.
6.
(Only visble if “Full automatic” is enabled)
Light dependent full automatic
: "Movement Local" object can turn on and off a
function base on both movement and the lux threshold switch (see chapter below).