background image

9

The Multi-Function DIP Switch 

The ASD-120 2.0 has a seven-position Multi-Function DIP switch array located 
under the security cover on the front panel to the left of the bypass DIP switch.   
The Multi-Function DIP switches are designated 1 through 7 from left to right and 
a label for programming can be found on the inside of security cover plate.  

This DIP switch is used to set the sequence delay time, active state of the FORCE 
OFF feature, and program the behavior of the remote interface.  The sequence 
delay time is controlled by DIP positions 1, 2, and 3, FORCE OFF is controlled by 
DIP position 4, and the remote interface behavior is controlled by DIP positions 5, 
6 and 7. The DIP switch settings are ON when in the UP position and OFF when in 
the DOWN position.  

Note: 

 The function of each switch is shown on a label located inside the F logo 

cover plate.  

ON

             DIP SETTINGS

DLY

ADJ

1    2    3    4     5    6    7 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

SET TO 
MIDDLE 
POSITION

ON

             DIP SETTINGS

DLY

ADJ

1    2    3    4     5    6    7 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

SET TO 
MIDDLE 
POSITION

DIP 4, 
FORCE OFF Settings 

DIP Switch position 4 is used to define how the ASD-120 2.0 will implement its 
FORCE OFF feature. FORCE OFF is a safety feature that is designed to cut AC 
power to all outlets instantaneously. Many municipalities require this feature as a 
means of disabling equipment in the presence of fire or alarm. The FORCE OFF 
inputs can be used with a momentary or maintained dry contact in either a Nor-
mally Open or Normally Closed state. The factory default position is DIP 4 ON or 
UP, or (NO) Normally Open. In this configuration, the FORCE OFF will be triggered 
when the FORCE OFF pins are shorted. If DIP Switch position #4 is on (DIP 4 OFF 
or DOWN) the FORCE OFF pins must remain shorted for normal operation. In 
this configuration, the FORCE OFF will be triggered when the short between the 
FORCE OFF pins is removed.

If a FORCE OFF occurs, the power to all outputs will be immediately disabled and 
the Delay Bank LEDs will blink together. To recover from a FORCE OFF condition, 
the ASD-120 2.0 must be sequenced off locally, by turning the key swich to the 
OFF position. Once reset, normal operations will resume. DIP 4 has priority over 
DIP 5, DIP 6, and DIP 7 settings. Information on DIP 5, DIP 6, and DIP 7 can be 
found in the following section.

The use of DIP 4 may or may not be a consideration for every install.  By default, 
DIP 4 is set to the ON (UP) position or (NO) Normally Open; meaning that the 
ASD-120 will operate normally with an open circuit applied to the FORCE OFF in-
put.  In this default setting, shorting the FORCE OFF pins will cause the ASD-120 
2.0 to go into FORCE OFF mode. 

DIP 1, DIP 2, and DIP 3: DIP Time Adjustment

DIP switch positions 1, 2 and 3  and the position of the DLY ADJ (Delay Adjust-
ment) pot control the time delay interval or “dwell time” between consecutive 
stages when sequencing ON or OFF.  The maximum time for each DIP switch is 
shown inside the cover plate label and represents the delay time when the DLY 
ADJ potentiometer is fully clockwise. DIP 1 adds 1 minute maximum time delay, 
DIP 2 adds 2 minutes and DIP 3 adds 4 minutes. Please note these time delays 
are cumulative. If all three DIP switches are in the UP position, the maximum 
allowable time delay will be 7minutes, i.e. 1min+2min+4min=7min. The factory 
default setting is DIP 1 ON or UP, and DIP 2 and 3 are OFF or DOWN. You can set 
these switches in any position you like to achieve your preferred time delay.

Delay Adjustment 

(potentiometer)

 

In order to precisely dial in your preferred sequence delay time, it is necessary 
to set the Time Delay Adjustment (DLY ADJ) located left of the multi-function DIP 
Switch. If this potentiometer is turned to its 100% value (fully clockwise), then the 
time delay will be equal to the maximum time delay defined by DIP switches 1, 2, 
and 3. If the potentiometer is in the 12 o’clock position (50%), then the time delay 
will be 50% of the maximum time delay interval defined by the setting of DIP 
Switch positions 1, 2 & 3. If all three DIP switches are off, and the potentiometer 
is turned completely counter-clockwise, the time delay is minimal. The Time Delay 
Adjustment potentiometer comes factory-set at 50%, the 12 o’clock position.

Example: If the DIP Switches are set to a 6 minute maximum delay and the po-
tentiometer is set to its 50% setting, then the delay interval between sequenced 
banks will be 3 minutes. (DIP 1 OFF or DOWN, DIP 2 and DIP 3 ON or UP = 6 
minutes) x .50 = 3 minutes.

1M 2M 4M

N.O.

N.C.

1    2    3   4    5    6   7 

ON

MOM

MNT

GND 

ON

12V ON

12V OFF

DELAY

1M 2M 4M

N.O.

N.C.

1    2    3   4    5    6   7 

ON

MOM

MNT

GND 

ON

12V ON

12V OFF

DELAY

Front                                                                         Back

  

DIP 5, DIP 6 & DIP 7   
Remote Mode Trigger Settings 

DIP 5 (+12V, ON OFF) and DIP 6 (GND ON) are used in special situations, where 
the factory-set remote options are not preferred. For instance, a newly remodeled 
location has an existing remote key switch different from a Furman remote key 
switch design, and it would be advantageous to use the existing key switch, since 
many personnel already have keys. DIP 5 (+12V, ON OFF) and DIP 6 (GND ON) 
could possibly address such situations. Please feel free to contact Furman, if 
further assistance is necessary.

DIP 7 is used to set the remote switching preference. The ASD-120 2.0 can be 
set to a Maintained Mode (DIP 7 OFF or DOWN) or a Momentary Mode (DIP 7 
ON or UP) dependent upon the chosen method of remote switching. A Main-
tained switch method stays open until switched, and then remains closed until 
switched again (such as toggle switches, e.g. Furman RS-1 key lock switch).The 
Momentary switch method is normally open and stays closed only as long as the 
button is depressed (such as pushbutton switches, similar to the Furman RS-2 
security switch).

Momentary Mode does offer an advantage over Maintained Mode when multiple 
remote switching locations are desired. Due to technical flexibility, Momentary 
switching easily adapts when implemented with more than one remote switch. 
However, maintained switching can be more stable, truly shunting control 
voltages when actuated. DIP 5 and DIP 6 offer additional methods of applying 
Maintained switching. Regardless of which switching method is chosen, when 
changing DIP 4, DIP 5, DIP 6, or DIP 7, it is required to reset the Key Switch to 
the OFF position before continuing the programming and installation.

Summary of Contents for ASD-120 2.0

Page 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Page 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Page 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Page 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Page 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Page 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Page 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Page 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Page 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Page 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Page 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Page 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Page 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Page 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Page 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Page 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Page 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Page 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Page 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Page 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Page 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Page 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Page 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Page 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Reviews: