background image

16

Configuration for Remote Operation

Maintained switches are generally most convenient when there is only one remote 
control location. The ASD-120 2.0 is shipped factory-set for Maintained On 
operation.  The alternate method of controlling the ASD-120 2.0 through the use 
of a momentary push button switches can be used when more than one remote 
switch location is required.

Note:

  The front panel Key Switch must be in the REMOTE position for ASD-120 

2.0 to accept commands. Furthermore, an ON or an OFF key position functions 
in either DIP 7 Maintained or Momentary mode bypassing all other program 
functions except the Bypass Set or a Force Off condition.

Maintained On - 12V ON/OFF      

When the Key Switch is in REMOTE mode, +12V present at the REM input with 
respect to GND will initiate an ON or OFF sequence depending on the position 
of DIP 5 (12V ON/12V OFF).  After the sequence is complete, the output circuits 
will remain in the configured state as long as +12V is present.  The source of the 
+12V can be from the remote interface itself, through remote relay contacts, or 
can be supplied by a +12V source from connected equipment.  The absence of 
12V will cause the ASD-120 2.0 to toggle, and remain in the opposite state. 

The ASD-120 2.0 cannot operate in the 12V ON/OFF Maintained Mode when DIP 
6 is set to the GND ON mode.  The GND ON switch will take priority.  In 12V ON/
OFF Maintained Mode, one cannot use the START ON/OFF SEQUENCE button. 
If someone does press the button, the ASD-120 2.0, if ON, will start an OFF 
sequence that will last until you release the button. 

Note:

  To disable the front panel button Start Sequence completely, the GND ON 

Maintained Mode should be used. 

Maintained On  - GND ON    

A simple connection from the REM terminal to the GND will initiate an ON se-
quence when DIP 6 is in the up position.  After the sequence is complete, 
the output circuits will remain in the configured state as long as the ground con-
nection to REM is present.  Opening this connection initiates the OFF sequence. 
When DIP 6 is set for GND ON, the position of DIP 5 12V ON/OFF is ignored. 

Note:

  The Start Sequence button has no effect when thw ASD-120 2.0 is in 

GND ON mode.

Maintained Off Mode      

In the Maintained Off Mode, the ASD-120 2.0 will sequence ON or OFF with the 
Key Switch or a remote activation trigger.  In this mode the ASD-120 2.0 will 
always remain in an OFF state until a connection is present between the REM 
and GND terminals or between the 12V and REM terminals.   

DIP #7 switch is set in the down position (MNT) for operation in Maintained 
Mode.  And when utilizing the REM and GND terminals, an ON response can be 
programmed by setting DIP switches #5 and #6 accordingly.  And when utilizing 
the 12V and REM terminals, the same is true. The connection to the REMOTE 
interface must exist, whether it be a presence or absence of 12V or open/closed 
contacts.  This mode is not typically used.  

Note:

 The Start Sequence Button is disabled when DIP 6 is in GND ON mode 

(Position UP).

Momentary Mode

In the Momentary Mode, a momentary switch such as the one located on the 
front panel of the ASD-120 2.0, or the Furman RS-2 remote switch panel, can 
be used to initiate an ON or OFF sequence.  The Momentary Mode is selected 
when DIP #7 (MOM/MNT) is in the up (MOM) position and DIP #6 (GND ON) is 
in the down position.  The position of DIP #5 (12V ON/12V OFF) is ignored.  In 
Momentary Mode, the ASD-120 2.0 will toggle between ON and OFF sequences 
every time a trigger is received from the front panel button or at the REM terminal 
with respect to GND.  Multiple Furman devices with a REMOTE interface can be 
synchronized by connecting the REM and GND terminals together.

When the ASD-120 2.0 has been configured for momentary mode, the REM 
connection at the rear panel can act as an input or output depending on which 
button is pressed.  If the ASD-120 2.0 button has been pushed, the REM 
connection provides a +12V output for as long as the button is depressed.  Any 
connected Furman products with REM and GND terminals will also cycle on or off.  
To synchronize all equipment connected together in this way, press the START 
SEQUENCE button for at least 6 seconds.  The outputs of all connected products 
will be shut off.  If the connected product is a sequencer, the Sequence OFF will 
be triggered.  If remotely triggered, the sequence starts on the rising edge of the 
signal at the REM terminal. 

All Furman products connected in this way must be configured for Momentary 
Mode. When first plugged in (or after power is lost and reapplied for any reason), 
the ASD-120 2.0 outputs will remain off until a momentary trigger is received at 
the REM input or the START SEQUENCE button is pressed.  Pressing the START 
SEQUENCE button while an ON or OFF sequence is in progress will result in an 
immediate change in direction of the sequence.

Note:

 Loss of AC Power in Momentary Mode will result in all Banks returning to 

an OFF state when the utility service is restored.

Summary of Contents for ASD-120 2.0

Page 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Page 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Page 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Page 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Page 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Page 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Page 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Page 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Page 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Page 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Page 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Page 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Page 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Page 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Page 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Page 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Page 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Page 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Page 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Page 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Page 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Page 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Page 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Page 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Reviews: