background image

3

120/208 3 Phase

5 Conductor

3 Conductors at 40A

Loss/ft (W) vs. % Load

120/240 Single Phase

4 Conductor

2 Conductors at 60A

Loss/ft (W) vs. % Load

AWG      100% Load   50% Load      100% Load       50% Load
     6         3.8 W/ft      0.9 W/ft                 NA               NA
     4         2.4 W/ft      0.6 W/ft          3.6 W/ft           0.9 W/ft
     2         1.5 W/ft      0.4 W/ft          2.3 W/ft           0.6 W/ft

If the equipment is to be portable, a common connection method is to permanent-
ly attach a short cable whip to the Furman and terminate it with a high-current 
connector.  A long feeder cable with a mating connector would then be prepared 
which could easily be disconnected for storage.   
 

3. Prepare and connect the AC supply: 

The AC supply cable will be connected to the internal bus bars via terminals that 
secure the individual conductors with set screws.  These terminals can accept 
wires as large as 2 AWG.  Strip one end of the cable to expose the wires.  When 
removing the outer jacket, be careful not to nick or cut into the insulation of the 
individual conductors.  When stripping the individual conductors, be careful not 
to cut through any of the copper strands. All of the individual conductors should 
be stripped one-half inch.  After threading the cable end through the strain relief 
clamp, connect the stripped conductors to the bus bar blocks.  Be sure to put 
each wire in the lower part of its terminal, so that it is compressed above and be-
low by copper rather than by the set screw itself.  Tighten the set screws securely.

Table 1 – Cable Loss Comparison

Prior to use, an appropriately sized power cable must be installed on the ASD-
120 2.0.  A qualified electrician should be employed for selection of cabling and 
installation.  Bus bars for the connection of AC input power are accessible when 
the top panel is removed.  One safety ground terminal is also provided.  The ASD-
120 2.0 is configured for 120/208 three phase power at time of shipment, but a 
120/240V single phase source can be supported.  Heavily loaded circuits can be 
re-distributed between phases to balance the load as necessary. 
 
The following instructions are provided as a guide for powering the ASD-120 2.0.  
All steps should be performed while the unit is disconnected from power and 
before it is installed in an equipment rack.  
 
 

1. Determine the power source to be used with the ASD-120.  

 

In North America, there are two possibilities: 120/208V three phase, and 
120/240V single phase (sometimes called “Single Split”).  Three Phase requires 
an additional conductor, but it provides better copper utilization.  A three phase 
source will require five conductors; X (L1), Y (L2), Z (L3), N, and Safety GROUND.  
The source must be a “Y” or “Wye” configuration and must include a star point 
neutral.  A 120/240V single phase source is connected with four conductors; 
X (L1), Y (L2), N, and Safety GROUND.  If the loads are balanced, the neutral cur-
rent will be zero, but if the load is predominately on one phase, the neutral must 
support the entire load current.  Since phases are distributed to different circuits 
a neutral conductor of the same gauge is the minimum recommendation, 
a licensed electrician may recommend a thicker gauge neutral based on other 
technical considerations.

2. Select a cable and determine its length.  

  
If the ASD-120 2.0 is installed in a permanent or semi-permanent location, it is 
possible to connect it with flexible metal-jacketed conduit.  A flexible type SOW 
or SOOW supply cable known as a “whip” is recommended for portable use. In 
three phase applications, the whip must carry a rating of 40 Amps minimum in 
each of three out of five conductors; and for a single phase 120/240 source, a 60 
Amp rated minimum for load current in two out of four conductors.  The minimum 
recommended conductor gauge is 6AWG for a 120/208 three phase source and 
4AWG for a 120/240 single phase source.

Cable efficiency losses per foot are listed in Table 1. Losses are dramatically 
reduced at lower currents since the losses are a function of the square of the 
current.  A larger cable size should be considered for critical loads that have high 
peak currents, such as power amplifiers.  Cable lengths can be longer if the load 
current is significantly below the rated maximum, and if large transient peaks are 
not expected.

4. Load Balancing:

The load should be balanced between phases.  As shipped, the load circuits are 
evenly divided among the X, Y, and Z bus bars in support of a balanced 120/208V 
three phase input.  If a 120/240 source is connected to the ASD-120 2.0, the Z 
bus bar is not used and the load conductors connected to this bus bar must be 
moved to the appropriate X and Y bus bars. (Please see Table 2.)

By default, there are two 12 AWG black conductors connected by Fast-On termi-
nals to each bus bar.  The black wires are labeled with a letter (A, B, C, D, E, or F) 
corresponding to the circuit to which it is connected.  Since the load is applied in 
a sequence, the loads should be alternately applied to each phase as determined 
by the position of the load phase conductors.
 
An example of how the loads should be connected is shown in Table 2.

POWER DISTRIBUTION BLOCK

MAX VOLTS: 240 VAC

MAX AMPS: 60A / PHASE

 

120A TOTAL

TORQUE SPECIFICATIONS

     AWG 

lb-in (N-m)

       2 

45 (5.1)

       3 

50 (5.6)

    4 - 6 

50 (5.6)

 INPUT 120 / 3Ø, 208 / 240 VAC 
14400 WATTS – 120 AMPS MAX

20A MAX

DELAY A

20A MAX

DELAY B

20A MAX

DELAY C

20A MAX

DELAY D

20A MAX

DELAY E

20A MAX

DELAY F

FORCE OFF

DELAY OUTPUTS

REMOTE

NC   A    B    C    D    E    F   NO

12V  STAT  REM  GND

WARNING! ELECTRIC SHOCK HAZARD. CONNECTION OF A POWER 

INPUT CABLE TO THIS DEVICE AND TO A POWER SOURCE MUST BE  

DONE BY QUALIFIED PERSONNEL ONLY.  

DANGER: MANIPULER SEL ON LES INSTRUCTIONS DU

 FABRICANT ET CONFIER LA MAINTENANCE A UN T 

ECHNICIEN QUALIFIE

DRY RELAY CONTACTS - RATING 48V / 1 AMP

WIRING INSTRUCTIONS

Summary of Contents for ASD-120 2.0

Page 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Page 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Page 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Page 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Page 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Page 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Page 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Page 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Page 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Page 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Page 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Page 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Page 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Page 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Page 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Page 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Page 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Page 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Page 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Page 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Page 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Page 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Page 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Page 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Reviews: