background image

20 Amp Thermal Circuit Breakers

The ASD-120 2.0 has six, 20 Amp thermal circuit breakers that protect each of 
the six individual Delay Banks (A through F).  The circuit breakers are located on 
the front panel immediately below the Bank Status LEDs.  Each of the six circuit 
breakers (A through F) correspond to a Delay Bank (A through F) 

If the combined current level plugged into a Delay Bank exceeds 20 Amps at any 
time, the circuit breaker will “trip”, the circuit breaker button will pop outward, and 
power will be cut to the devices connected to that particular Delay Bank. 

If a breaker “trips”  the user should review the load that is connected to the 
offending Delay Bank and make adjustments as necessary to reduce load to 
below 20A.  To reset the breaker simply press the button in.  Please note that 
the breakers are thermally activated.  It is best to wait a few minutes to allow the 
breaker to cool before attempting to reset it. 

8

ON

             DIP SETTINGS

DLY

ADJ

1    2    3    4     5    6    7 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

SET TO 
MIDDLE 
POSITION

REMOTE

OFF                                  ON

Key Switch - 3 position ON/OFF Security Switch

The ASD-120 2.0 has a three position key switch that functions as a Local ON 
Local OFF, and Remote interface selection switch.  When the key is in the ON po-
sition, the ASD-120 2.0 will sequence all Delay Banks on and remain on.  When 
the key is in the OFF position, the ASD-120 2.0 will sequence all Delay Banks OFF 
and remain off.  When the key is in the REMOTE position the ASD-120 2.0 will 
operate according to the signal presented at the remote interface and the action 
of the front panel START SEQUENCE button. 
 
If the key switch is in the REMOTE position and no signal is presented on the 
rear panel Remote interface, the ASD-120 2.0 will operate according to the front 
panel START SEQUENCE button.  If the DELAY BANKS are off, pressing the START 
SEQUENCE button will cause the DELAY BANKS to sequence on.  If the DELAY 
BANKS are on, pressing the START SEQUENCE button will cause the DELAY 
BANKS to squence off.  If the key switch is rotated from REMOTE to the ON or 
OFF position, the ASD-120 2.0 will sequence ON or OFF according to the final 
position of the key switch.

When the key switch is in the REMOTE position, the ASD-120 2.0 can accept on/
off commands from the rear panel 4-Pin Remote interface.  The operation of the 
remote interface is explained elsewhere in this manual. Please note that the ON 
or OFF key switch positions defeat the rear panel remote interface. 

ON

:  ON: Banks sequence ON and remain ON except 

those configured as “ALWAYS OFF” with the bypass 
switch.

OFF

: Banks sequence OFF and remain OFF except those 

configured as “ALWAYS ON” with the bypass switch.

REMOTE: 

 Accepts On/Off signals through the rear 

panel REMOTE connector and the front panel START 
SEQUENCE push-button switch.

Security Cover Shield and DIP Switch Program Interface  

The ASD-120 2.0 had two configuration DIP switches that are located underneath 
a security cover near the center of the front panel.  The two DIP switches are used 
to set various sequencer options.  You will need a small Philips screwdriver to 
remove two 6-32 

3

/

8

” Philips screws to gain access to these switches.   

The ASD-120 2.0 comes with the security cover pre-installed to protect against 
unauthorized configuration changes.  The security cover is intended to discourage 
unauthorized personnel from tampering with or adjusting set programming once 
the unit has been installed. The security cover is attached to the front panel using 
two 6-32 

3

/

8

” Philips head screws.  Please use only the two screws provided for 

attaching the security cover.

Note:

  Other types of tamper-resistant screws may be preferable depending on 

the desired level of security. Please do not exeed the 

3

/

8

” length restriction.

The Sequence Bypass DIP Switches

The ASD-120 2.0 has a six-position, three-state DIP switch located under the 
security cover on the front panel to the right of the multi – function DIP switch.  
The sequence bypass switch is used to bypass the sequencing on any or all of the 
DELAY BANKS. The sequence bypass switch is an array of six tri-state switches, 
and each tri-state switch has three possible positions (ON. OFF, and SEQUENCE).  

When the switch is set to the ON (“Always On”) position, the corresponding 
DELAY BANK will be ON regardless of the state of the sequencer. When the switch 
is set to the OFF (Always Off”) position, the corresponding DELAY BANK will be 
OFF regardless of the state of the sequencer. When the switch is set to SEQ 
(“Sequence”), the corresponding DELAY BANK will follow the state of the 
sequencer.

Note that FORCE OFF mode has priority over the sequence bypass DIP switches.  
When the ASD-120 2.0 is in FORCE OFF mode, all banks will be disabled regard-
less of the state of the sequence bypass DIP switches.

DIP position ON (A thru F) = Delay Bank and Relay is ALWAYS ON
DIP position SEQ (A thru F) = Delay Bank and Relay activates in Sequence
DIP position OFF (A thru F) = Delay Bank and Relay is ALWAYS OFF

Note:

  Except for a Force Off condition, the Sequence Bypass DIP Switch 

overrides any local or remote switch function.

START

 

SEQUENCE

REMOTE

DLY

ADJ

DELAY A                               DELAY B   

               DELAY C

PHASE 

X             Y            Z

DELAY D                               DELAY E   

               DELAY F

OFF                                  ON

1  2  3  4  5  6  7 

ASD-120 2.0

120 AMP POWER SEQUENCER

(SEE COVER PLATE) 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

START

 

SEQUENCE

REMOTE

DLY

ADJ

DELAY A                               DELAY B   

               DELAY C

PHASE 

X             Y            Z

DELAY D                               DELAY E   

               DELAY F

OFF                                  ON

1  2  3  4  5  6  7 

ASD-120 2.0

120 AMP POWER SEQUENCER

(SEE COVER PLATE) 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

START

 

SEQUENCE

REMOTE

DLY

ADJ

DELAY A                               DELAY B   

               DELAY C

PHASE 

X             Y            Z

DELAY D                               DELAY E   

               DELAY F

OFF                                  ON

1  2  3  4  5  6  7 

ASD-120 2.0

120 AMP POWER SEQUENCER

(SEE COVER PLATE) 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

1M

2M

4M

N.O.

N.C.

1    2    3   4    5    6   7 

ON

MOM

MNT

GND 

ON

12V ON

12V OFF

DELA

Y

Summary of Contents for ASD-120 2.0

Page 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Page 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Page 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Page 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Page 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Page 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Page 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Page 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Page 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Page 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Page 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Page 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Page 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Page 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Page 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Page 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Page 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Page 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Page 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Page 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Page 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Page 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Page 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Page 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Reviews: