Automatic Voltage Regulation (AVR) Mode
Sensitive AVR setting: when receiving input voltages of 96 VAC – 135 VAC, the F1500-UPS supplies a regulated voltage of 120
VAC ± 5%.
Standard AVR setting: when receiving input voltages of 93 VAC – 145 VAC, the F1500-UPS supplies a regulated voltage of 120
VAC ± 10%.
AVR OFF setting: AVR is disabled, no voltage correction.
UPS Mode
In the event of a loss of power to the unit, over-voltage, or under-voltage, the F1500-UPS will function as a battery back-up. An
audible alarm will sound and the display will indicate the fault (lost power, over-voltage, under-voltage) as well as the number of
minutes of battery life remaining.
Setup Mode
The setup menu allows the user to adjust several of the operating parameters of the unit.
Please refer to diagrams on page 58 for a detailed map of the menu structure.
Setup Menu Navigation
Clockwise (CW) rotation of the navigation dial advances the menu to the next item. If the menu is at the last item, SYSTEM INFO,
return to Normal Operation Mode. Counter clockwise (CCW) rotation of the navigation dial sends the menu to the previous item.
If the menu is at the first item, DISPLAY BRIGHTNESS, the menu will return to Normal Operation Mode. Pressing the navigation
dial selects the current menu item. If there is no activity of the navigation dial for 60 seconds, the menu will automatically return
to Normal Operation Mode.
Parameter Selection and Adjustment
CW rotation of the navigation dial INCREASES the selected parameter, or advances to the NEXT available value. CCW rotation of
the navigation dial DECREASES the selected parameter, or goes back to the PREVIOUS value. Pressing the navigation dial selects
the current parameter value. If there is no activity of the navigation dial for 60 seconds, the menu will return to Normal Operation
Circuit Breakers for Overload Protection
Resettable circuit breakers provide optimal overload protection.
RS-232 Serial Communication Port
The serial port allows connection and communication between the F1500-UPS and an automation, media server, or computer
system. This allows the installer to program a number of variables including the Critical Load Battery Threshold. See the software
documentation for more information.
AC Power Cord
Captive, heavy-duty shielded power cord.
USB to Computer
USB port allows communication between F1500-UPS and computer.
OPERATING MODES
Normal Operation (Utility Power) Mode
When connected to a live power source, the F1500-UPS provides power and is ready to provide protection from under- and over-
voltages.
Rotate the navigation dial to scroll through the screens.