2. WIRING
2-39
2.7.3
How to set jumper blocks in the sensor adapters
MC-3000S
Set the jumper blocks in the MC-CS Board (24P0114) referring to the tables that
follow.
MC-CS Board (24P0114)
Jumper block:
Use the jumper block J19 to set the termination resistor on/off for the MODBUS com-
munication on the connector J1. For the first and last sensor adapter in a series, their
termination resistors should be set to ON. Use the MC-CS Board with the default set-
ting because it becomes the “first” adapter in a series.
Set the jumper blocks J14 through J17 to turn the termination resistors on connectors
J4 through J7 respectively.
Jumper block J19
Connector J1
1-2
SHORT
Termination resistor: ON (default setting)
2-3
OPEN
1-2
OPEN
Termination resistor: OFF
2-3
SHORT
S2
J14 J22 J23 J15 J16 J17
J19
J20 J21
(Not used)
(J20/J21 are not used)
(J22/J23 are not used)