11
System Components
Carbon Filter Control Valve Features
Setting the Time of Day
1. Press and hold either the Up or Down buttons until the programming icon replaces the
service icon and the parameter display reads TD.
2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button to resume normal opera-
tion. The unit will also return to normal operation after 5 seconds if no buttons are
pressed.
Queueing a Backwash
1. Press the Extra Cycle button. The service icon will flash to indicate that a backwash is queued.
2. To cancel a queued backwash, press the Extra Cycle button.
Backwashing Immediately
Press and hold the Extra Cycle button for five seconds.
Time Clock Delayed Control
A Time Clock Delayed Control regenerates the system on a timed interval. The control will
initiate a backwash cycle at the programmed backwash time when the number of days
since the last backwash equals the backwash day override value.
Day of the Week Control
This control regenerates the system on a weekly schedule. The schedule is defined in Mas-
ter Programming by setting each day to either "off" or "on." The control will initiates a regen-
eration cycle on days that have been set to "on" at the specified regeneration time.
Control Operation During Programming
The control only enters the Program Mode with the valve in service. Control programming
is stored in memory permanently, eliminating the need for battery backup power.
Manually Initiating a Backwash
1. When timer is in service, press the Extra Cycle button for 5 seconds on the main screen.
2. The timer advances to Backwash Cycle Step #1 (backwash), and begins programmed time
count down.
3. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #2 (brine
rapid rinse).
4. Press the Extra Cycle button once more to advance the valve back to in service.
Installation, Operation and Maintenance Manual
Oxi-Gen Oxi-2P,3P,4P, 5P & 6P System