background image

FuturaSun srl – The specifications in this manual are subject to revisions without further notice  

7. Installation 

7a) Module Mounting 

 

The FU modules are qualified for an operative 
temperature within the range of -40 to +85 °C.  

 

 

The  FU  modules  can  be  installed  at  a 
maximum operating altitude of ≤ 7000 meters. 

 

  When  installing  FU  modules,  local  building 

code  requirements  and  regulations  must  be 
adhered to at all times. Sufficient ventilation of 
the  module  backside  is  required  and  the 
mounting 

configuration 

(e.g. 

sufficient 

clearance) should be adapted accordingly

.

 

 

Do  not  drill  any  additional  holes  into  the 
module  frames  and  do  not  cover  the 
drainage holes

.  

 

Pre-assembled  mounting  systems  have 
been confirmed by FUTURASUN in writing 
in advance 

  The  modules  can  be  mounted  in  every  angle 

from 

horizontal 

to 

vertical, 

avoiding 

configurations  with  the  junction  box  up-side 
down  at  all  times  (e.g.  trackers  with  “sleep 
mode”).  

  In order to maximize module exposure to direct 

sunlight, the modules should be oriented to the 
south  in  the  northern  hemisphere  and  to  the 
north in the southern hemisphere. 

 

Mounting Methods: 

Mounting using mounting holes: 

  Each module must be securely fastened at 

a minimum of 4 points.  

  Use the 4 mounting holes (slots, see Fig. 4) 

on the PV module frame to bolt the module 
with stainless steel screws and nuts to the 
mounting framework.  

  The  distance  of  the  mounting  holes  has 

been  designed  in  order  to  result  in  a 
uniform  wind  and  snow  load  without 
damaging the module.  

  Do not drill additional holes in the module 

frame; doing so will void the warranty.  

 

Mounting using clamping method: 

  FUTURASUN  recommends  the  use  of 

clamps. 

  When using clamps, it is possible to mount 

the modules in horizontal (the shorter side 
of one module facing the shorter side of the 
neighboring  module)  or  in  vertical  (the 
longer 

sides 

facing 

each 

other) 

configuration.  (It  is  recommended  to 
always  use  stainless  steel  screws  and 
bolts.) 

  The  modules  can  be  mounted  on 

continuous  base  structures  (inclined  or 
horizontal) such as rails or similar. 

  Both base structures  must be  mounted  at 

the  same  distance  from  the  symmetrical 
axis (vertical or horizontal) of the module. 

  In  vertical  configuration,  it  is  strongly 

recommended  to  place  the  supporting 
elements nearby the mounting holes, or in 
any  case,  the  distances  shown  in  Fig.  3 
should be respected. This is necessary in 
order to maintain a correct load distribution.  

  The FU XXX P modules with both 60 and 

72 cells are qualified to 3600 Pascal x 1,5 
safety factor in wind and snow load when 
the module is fixed in the green and yellow 
area (See Fig. 3) 

  The FU XXX M modules of size 72 cells are 

qualified to 1600 Pascal x 1,5 safety factor 
in wind and snow load when the module is 
fixed in the green and yellow area (See Fig. 
3) 

  The FU XXX M modules of size 60 cells are 

qualified to 3600 Pascal x 1,5 safety factor 
in wind and snow load when the module is 
fixed in the green and yellow area (See Fig. 
3) 

  In according with Eurocodes - EN 1991 it is 

not  possible  to  fix  the  modules  in  yellow 
area  (See  Fig.  3)  in  Zone  3,4,5  of  Alpine 
Region. Shape coefficients must be taken 
into account. 

  In  horizontal  configuration,  fixing  the 

modules  by  blocking  them  at  the  4 
mounting  holes  will  guarantee  the 
characteristics regarding the static loads as 
certified. 

  When  clamping  the  modules  in  horizontal 

configuration  on  a  support  structure,  the 
distances  in  Fig.  3  have  to  be  applied  in 
order  to  maintain  the  resistance  against 
static loads as certified: 

  The modules can also be fixed by placing 

them with their frame on a structure that is 
supporting the two sides of the frame over 
their  whole  length.  Also  in  this  case,  the 
position of the mounting clamps must be in 
accordance with distances indicated in Fig. 
3.  

  At least 20 mm spacing must be maintain 

between modules 

 
 

ATTENTION

:  in  the  case  of  installation  with 

modules in the vertical position, it is preferable to 
maintain the Junction Box located in the upper part 
of  the  module.  This  practice  will  help  reduce,  as 
much as  possible,  contact  between  any  standing 
water  and  the  Junction  Box,  and  avoid  possible 
water infiltration. 

 
 

Summary of Contents for FU M Series

Page 1: ...Author FuturaSun Document name Installation_manual_FuturaSun_2017 Revision date 07 08 2017 SAFETY AND INSTALLATION MANUAL Photovoltaic Module FU XXX P M...

Page 2: ...notice CONTENTS 1 General Information 3 2 Disclaimer of Liability 4 3 IEC 61215 61730 certifications 4 4 Limited Warranty 4 5 Module Specification 4 6 Safety Precautions 4 7 Installation 5 8 Use and...

Page 3: ...maximum power Impp Power Pmax with tolerance of 3 Solar radiation in W m2 at the time Temperature of the modules The general performance of the modules is heavily dependent on the intensity of the inc...

Page 4: ...allic jewelry and use insulated tools during installation Do not expose the modules to artificially concentrated sunlight Do not stand on drop scratch or allow objects to fall on the modules Do not li...

Page 5: ...on continuous base structures inclined or horizontal such as rails or similar Both base structures must be mounted at the same distance from the symmetrical axis vertical or horizontal of the module I...

Page 6: ...he mounting holes the drainage holes and the ground connection holes See the table of 60 and 72 cell module Mechanical drawing 60 cell module Mechanical drawing 72 cell module 7b Handling of Modules T...

Page 7: ...PV module is likely to experience conditions that produce more current and or voltage than reported at STC Accordingly the values of Isc and Voc marked on the module should be multiplied by a factor...

Page 8: ...will be approximately equal to Vocmod VocSTC Tmod 25 C x 0 125V Where o VocSTC is the open circuit voltage measured at STC o 0 125V C is the average variation of Voc of a module for a variation in tem...

Page 9: ...tion from mechanical stresses 9b How to Manage the Packaging Each package has been designed to allow the shipment and storage of modules in order to maintain their integrity unchanged over time provid...

Page 10: ...t During the handling of the pallet make sure to pay the utmost attention The packaging must be raised moved exclusively with fork lift trucks or hand pallet trucks fitted with forks of length appropr...

Page 11: ...isions without further notice 10 Temperature coefficients Technical data FU XXX P FU XXX M Voc temperature coefficient C 0 285 0 273 Isc temperature coefficient C 0 0474 0 0344 Pmax temperature coeffi...

Reviews: