FuturaSun srl – The specifications in this manual are subject to revisions without further notice 
This document applies to the module series FU XXX M ZEBRA 

  In a case that the V

oc

 to the connectors is 

decidedly  lower  than  the  standard  values 
(75%  or  less)  this  could  represent  a 
condition  of  anomaly  which  should  be 
investigated more thoroughly. 

 
To measure the short-circuit current (I

sc

):  

  A  PV  module  exposed  to  the  south, 

inclined perpendicularly to the rays of the 
sun, in the middle of the day (about 12:00 
to  1:00  PM  )  and  in  conditions  of  good 
weather, presents a value of I

sc

 similar to 

the  rated  values  at  STC,  as  measurable 
with an amp-meter in continuous current.  

  By  measuring  the  solar  radiation  (E) 

effective  at  the  moment  with  a 
solarmeter/pyranometer in W/m

2

 the short 

circuit current of the module at the moment 
I

scmod

 should be very close to the following 

value: 

 

I

scmod

 = I

scSTC

 x E/1000 

Where:  

o

  I

scSTC

  is  the  short  circuit  current 

measured at STC;  

o

  1000 W/m² is the radiation at STC. 

 

  The measurement of the Isc is executable 

with  precision  only  when  using  a 
solarmeter/pyranometer which gives exact 
information  on  the  conditions  of  solar 
radiation at the moment, otherwise it is not 
reliable.  

  In  the  case  of  the  unavailability  of  a 

solarmeter/pyranometer,  it  will  only  be 
possible  to  have  an  estimate  of  the 
functionality  of  the  module  by  comparing 
the  value of  I

scmod 

measured  in  relation  to 

those  of  the  other  modules  of  the  PV 
system,  measured  under  the  same 
conditions of irradiation.  
The  acknowledgment  of  any  obvious 
discrepancies  of  I

sc

  in  the  modules  thus 

serves to identify anomalies. 

 

 

The  maximum  module  configuration 
when connected in series is 21 modules 
size  120  half-cut  cells,  for  1000  V  DC 
systems 

 

The  maximum  module  configuration 
when connected in series is 31 modules 
size  120  half-cut  cells  for  1500  V  DC 
systems 

 

For parallel connections, the maximum 
configuration is 2 strings  

8c) Maintenance 

Although  PV  modules  do  not  require  any 
routine  maintenance,  periodic  (annual) 
inspection for damage to glass and inspection 
of the electrical connections and for corrosion 
as  well  as  the  mechanical  connection  is 
recommended.  
 
Under  normal  conditions  (sufficient  rainfall), 
cleaning  of  the  module  is  not  required.  In 
extreme  climatic  conditions,  the  electrical 
performance of the module may be affected by 
accumulation of dirt on the glass front cover.  
In  this  case,  the  front  cover  can  be  washed 
using water (no aggressive cleaning solutions, 
chemicals or abrasives) and a soft cloth.  
 
Exercise extreme caution when applying water 
on any electrical device!! 
 
 

ATTENTION!!!!! 

 

To  avoid  the  phenomena  of  electric  arcing, 
both the connection and disconnection of the 
connectors  of  the  modules  being  tested  and 
the  measurements  of  Voc  should  be 
performed  with  the  string  of  modules  in 
conditions of open circuit. 
 
In  addition,  the  Isc  should  be  measured  for 
each  individual  module  in  conditions  of  short 
circuit  

9.  Packaging,  Handling  and  Storage  of 
Modules 

9a) FUTURASUN's Packaging 

 
FUTURASUN provides the FU modules in the 
most  appropriate  packaging,  designed  to 
guarantee that the transportation and storage 
will  be  in  conditions  of  maximum  safety  and 
protection  until  the  time  of  installation. 

Transport  the  module  in  its  original 
packaging until installation.

 Protect all parts 

of the module during transport and installation 
from mechanical stresses. 

Summary of Contents for FU M ZEBRA Series

Page 1: ...Author FuturaSun Document name Installation_manual_FuturaSun_2020 Revision date 01 09 2020 SAFETY AND INSTALLATION MANUAL Photovoltaic Modules FU XXX M ZEBRA...

Page 2: ...cument applies to the module series FU XXX M ZEBRA CONTENTS 1 General Information 3 2 Disclaimer of Liability 4 3 IEC 61215 61730 certifications 4 4 Limited Warranty 4 5 Module Specification 4 6 Safet...

Page 3: ...current as snapshots which enable you to monitor the operation of the modules and determine possible although rare anomalies The electrical output parameters for FU modules of technical importance dur...

Page 4: ...dards cover flat plate PV modules and panels intended for installation on buildings or those intended to be freestanding This product is not intended for use where artificially concentrated sunlight i...

Page 5: ...constitute an increased risk of electric shock and may cause injury or death Modules shall not be connected in series to create strings with a higher voltage than the maximum system design voltage and...

Page 6: ...load and 2400 Pascal 3600 including a safety factor of 1 5 wind load when the module is fixed in the green area See Fig 4 and following The FU XXX M ZEBRA modules regardless of half cut cell configur...

Page 7: ...ion with half cut cells the yellow areas allow for a typical load of 2400 1600 Pa 3600 2400 Pa maximum including 1 5 safety factor The red areas are not allowed for clamping and fixing Fig 5 Mechanica...

Page 8: ...ZEBRA 132 half cut cells Color min max Green 1 355 555 Yellow 1 0 728 Red 1 728 1092 Yellow 2 0 149 Red 2 149 847 1 on long side of frame 2 on short side of frame tolerance 2 mm Fig 7 Mechanical drawi...

Page 9: ...main power supply may only be performed by authorized and qualified persons Before connection of the system to the grid the PV system must be approved for correct installation by an electrician respon...

Page 10: ...the Voc and Isc When the PV modules are instead connected in series parallel configuration to an inverter from its display it is possible to read Operational voltage at maximum power output Vmpp of th...

Page 11: ...rves to identify anomalies The maximum module configuration when connected in series is 21 modules size 120 half cut cells for 1000 V DC systems The maximum module configuration when connected in seri...

Page 12: ...he connectors degrading the characteristics and altering the electrical properties of the contacts of the module causing damage DO NOT OVERTURN THE PACKAGING the packaging is only designed to be handl...

Page 13: ...following procedures for the unpacking of modules Place the packaging on a stable and flat surface Using a cutter cut the plastic wrap surrounding the package or to open the paper box Remove the plas...

Reviews: